Operating status
Fault
6
Accessories
6.1
Inverter off
When using suitable KACO inverters, the shutdown can be carried out via the grid separation relay integrated into the
inverters and the "Inverter OFF" digital output instead of via interface switch.
Information about the "Inverter off" function: See manual under
the "Hybrid and battery inverter" category.
7
Maintenance and troubleshooting
Repairs may only be carried out by the authorized electrician.
NOTE
Log all maintenance activities in the "Service" menu item: "Service log" (exception: "User" interface). Config-
uration is carried out via the web interface.
7.1
Visual inspection by the operator
1 Inspect the product and cables for visible external damage and note the operating status display, where applicable.
2 Notify the installer if there is any damage.
8
Cleaning
8.1
By operator
CAUTION
Risk of damage to the device during cleaning!
Do not use compressed air or high-pressure cleaners.
Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top of the de-
vice on a regular basis.
Remove dust from the ventilation inlets if necessary.
F Clean the housing.
8.2
By authorized electrician
WARNING
Risk of injury from starting fans!
If the device is not completely disconnected from the voltage source, the fan may start up unexpectedly and
sever or injure limbs.
Make sure that the device is disconnected from all voltage sources before starting work on the device.
After disconnecting from all voltage sources, wait at least 5 minutes before starting maintenance ac-
tivities.
The maintenance activities listed may only be performed by qualified specialist personnel. For further information on
this and the maintenance tasks listed:
See manual under
http://www.kaco-newenergy.com/de/downloads
1 Clean the heat sink.
2 Replace the fan.
3 Replace DC fuse
4 Replace the overvoltage protection.
Side 142
LED Symbol
Description
The red "Fault" LED is illuminated.
Fault in the AC/DC source
Conditional special cases:
ž
There is no DC voltage present (e.g. DC isolator switch open)
ž
DC voltage too low (< starting voltage)
ž
DC voltage is present (> starting voltage), but communications con-
nection between the front end (operating unit) and back end (con-
trol unit) is faulty, or interrupted.
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
http://www.kaco-newenergy.com/de/downloads
in the "Hybrid and battery inverter" category.
in