10.5 Requirement for supply lines and fuse
DC-Seitig
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Cable lug dimension w width max
Length of insulation to be stripped off
Recommended cable type
Cable lug Ø connection bolt
Tightening torque
Fitting for DC connection
Torque for cable fitting
AC-side
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Length of insulation to be stripped off
Cable lug Ø connection bolt
Tightening torque
Connection type
Cable lug dimension w - maximum width
Ground conductor connection
Ground conductor connection tightening torque
Fuse protection for installation provided by customer (max
output overcurrent protection)
Fitting for AC connection
Torque for cable fitting
Side 146
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
240mm² (AL or CU)
in accordance with local installation standards
16 - 28 mm
42 mm
Depending on the cable lug
Solar cable
Bore for M10 screw
30
M40
10 Nm
240mm² (AL or CU)
in accordance with local installation standards
16 - 28 mm
Depending on the cable lug
Bore for M10 screw
10 Nm
Cable lug (use the appropriate cable lug depending on
the cable material!)
42 mm
M10
10 Nm
max. 250A
M40
10 Nm