↻ The device has been installed on the mount.
1 Strip the cable for equipotential bonding.
2 Furnish the stripped cable with an M8 ring cable lug.
3 Check that the connected cable is fitted securely.
» The housing is included in the equipotential bonding.
4.7
Connecting the interfaces
4.7.1 Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injuries or death may result from improper use of the interface connections and failure to observe
protection class III.
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with
protection class III.
All interfaces are located on the communication circuit board (HMI board) inside the housing.
1
Fig. 9: Communication circuit board (HMI board)
1
Communication circuit board
2
USB socket
3
SD- Slot
4
Ethernet for network connection DHCP
4.7.2 Connecting via Ethernet
NOTE
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is installed.
For this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the
cable fitting through the sealing insert.
NOTE
Use a suitable category 7 network cable. The maximum distance between two devices is 100 m (328 ft). The
Ethernet switch allows for the repeater function and supports auto-sensing. Ensure that the cable is cor-
rectly assigned. You can use both crossed and 1:1 protectively-wired Ethernet connection cables.
↻ Connecting cable inside the device.
1 Plug in an Ethernet cable at one of the two Ethernet ports on the communication circuit board.
Side 140
USB
SD Card
2
blueplanet gridsave 92.0 TL3-S blueplanet gridsave 110 TL3-S blueplanet gridsave 137 TL3-S
1x RJ 45
7
2x RJ 45
-+
-+
3
4
5
INV OFF - connection for remote controls -
24V(+/- 20%) /1A (at least 15mA)
6
ERR connection for external grid protection com-
ponent (fault signal relay)
7
Etthernet – only for starting up by means of static
IP(Start-up via cable connection)
1
Fig. 8: Additional earthing point
1 Earthing bolt
RS485
A
B
GND
RS485
INV
ERR
OFF
- +
A
B
A
B
GND
GND
5
6