Descargar Imprimir esta página

Franklin Electric COVERCO QC-AV Manual Del Usuario página 12

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
Disposal
Comply with the local regulations and dispose the control device as provided for the
by the aforementioned regulations. This product contains electrical and electronic
components and should be disposed of accordingly.
Technical specifications
Mechanical specifications
Class of protection
Environment
Installation height
Mounting
Storage temperature
Operating environment
temperature
Air humidity
Electrical specifications
Rated voltage
Rated insulation voltage
Short-term current
Rated conditional short
circuit current
Power
Standards
IEC/EN 61439-1
12
COV BOX M, QC/AV, QC/AVE
IP 50
Environment B pursuant
to IEC/EN 61439-1
max. 2000 m above sea
level
Wall mounting
from -25°C to +55°C
from -5°C to +55°C
50% at 55°C (without
condensation)
1~ / 50Hz
220 - 240V ±10%
400V AC
1,5 kA
1 kA
0,37 - 4,0 kW
Doc. Name: ManualeQuadriControllo2018 / Rev. Date: 3/10/2018
COV BOX T
IP 50
Environment B pursuant
to IEC/EN 61439-1
max. 2000 m above sea
level
Wall mounting
from -25°C to +55°C
from -5°C to +40°C
50% at 55°C (without
condensation)
3~ / 50Hz
380V -10% / 415V +6%
400V AC
50 kA
50 kA
0,37 - 7,5 kW

Publicidad

loading