If you want to apply a clock (or more simply a switch) to open and keep open
the gate, you have to take T2 24V with fw 02.
If fw 03 or higher ATTENTION: IN CASE OF FAILURE OF ONE SAFETY, ONE
MINUTE AFTER THAT CLOCK OR SWITCH HAVE BEEN ACTIVATED, THE GATE
WILL OPEN WITHOUT SAFETIES ACTIVE!
This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of workers,
emergencies in parking or residential areas and, temporarily, for moving operations).
CLOCK FUNCTION APPLICATION
It is necessary to request a T2 24V control panel with firmware 02. By connecting a switch
and/or a daily/weekly clock (instead of or in parallel to the open button N.O. "COM-OPEN"), you can
open and keep the automation open for as long as the switch is pressed or the clock remains active.
Command functions are inoperative with open automation. Releasing the switch or at the preset time,
the automation closes immediately.
CLOSE BUTTON (COM-CLOSE)
Controls the closing movement when the gate is stationary.
REMOTE CONTROL
If DIP 6 OFF => It cyclically performs the commands open-stop-close-stop-open etc.
If DIP 6 ON => Opens the gate when closed. There is no effect if activated while opening. If activated
when gate is open, the gate closes. If activated while closing, the gate reopens.
PEDESTRIAN OPEN BUTTON (COM-PED.BUTT.)
Partial opening and closing control. During pedestrian opening, pausing or closing, you can control
the opening of any command linked to the T2 24V board.
With DIP 6 you can choose the operation mode of the pedestrian push button.
If DIP 6 OFF => It cyclically performs the commands open-stop-close-stop-open etc.
If DIP 6 ON => Opens the gate when closed. There is no effect if activated while opening. If activated
when gate is open, the gate closes. If activated while closing, the gate reopens.
ELECTRIC LOCK (LOCK)
Set DIP 8 to ON to enable control of the electric lock when opening.
ELECTRIC LOCK PULSE RELEASE IN OPENING
Set DIP 9 to ON to enable the electric lock pulse release when opening (provided DIP 8 is ON).
If a command to open the gate is given when the gate is closed, the closing movement is performed
for 0.5 seconds and the electric lock is simultaneously activated (followed by a 0.5 second pause and
then the opening of the gate).
ELECTRIC LOCK PULSE ENGAGEMENT
Set DIP 10 to ON to enable the pulse engagement of the electric lock when closing. Upon closing,
motors are activated for 0.5 seconds at full voltage to ensure lock engagement.
EASY MOTOR RELEASE
Set DIP 11 to ON to enable easy manual release (provided that DIP 10 is ON), upon closing a reverse
motion with a fixed time of 0.2 seconds occurs to facilitate manual release.
O
PERATION OF SAFETY ACCESSORIES
PHOTOCELL (COM-PHOT)
DIP 4 OFF => if an obstacle is placed in range of the photocells when the gate is closed, the gate
does not open. During operation, photocells work when opening (by starting the
opening movement only after the obstacle is removed) and closing (by starting the
reverse movement only after the obstacle is removed).
DIP 4 ON => if an obstacle is placed in range of the photocells when the gate is closed and the
command to open is given, the gate opens (the photocells do not work while opening).
Photocells work only during closing (with reverse motion restored after a second, even
if they are still engaged).
CONTROL OF IMMEDIATE CLOSING AFTER MOVEMENT IN FRONT OF PHOTOCELLS
DIP 16 ON and DIP 4 OFF => if photocells are engaged during opening, the gate stops and the gate
only closes one second after the photocells are disengaged.
DIP 16 ON and DIP 4 ON => if photocells are engaged during opening, the gate continues to open.
Upon disengagement of the photocells, the gate stops and reverses
closing motion after a one second pause.
If total opening is reached (end of opening time), immediate closing is deactivated and
automatic time closing is activated (if TCA trimmer is activated and LED DL6 is on). If during
closing there is a rapid movement (e.g. pedestrian) the gate will open again for two seconds
and then close once again.
DIP 12 OFF => immediate closing after movement in front of the photocells is deactivated.
N.B.: Please check photocell operation at least every six months.
EDGE (SAFETY STRIP) (COM-EDGE)
If engaged during opening, reverses the motion when closing.
If engaged when closing, reverses the motion when opening.
If it remains engaged again, it performs a further reversal after 2 seconds, then performs an additional
short reversal and then gives the sensor failure or engaged alarm (N.O. contact).
If the sensor remains engaged (N.O. contact) no movement is allowed.
If not used, jump the terminals COM-EDGE.
MONITORING OF SAFETY SENSORS (A+ TEST A-)
Sensors can be monitored through the A+ TEST input and DIP 12 ON.
The monitoring consists of a functional test of the sensor run after every full gate opening.
Closing the gate is therefore permitted only if the sensors have passed the functional test after each
opening.
CAUTION: MONITORING OF THE SENSOR INPUT CAN BE ACTIVATED WITH DIP 12 ON OR
DEACTIVATED WITH DIP 12 OFF. IN FACT, THE FUNCTIONAL TESTING OF SENSORS IS 'POSSIBLE
ONLY IF THESE DEVICES HAVE THEIR OWN POWER SUPPLY.
A MECHANICAL SENSOR CAN NOT BE MONITORED, SO DIP 12 SHOULD BE SET TO OFF.
SENSOR AUTOTEST ALARM (DIP 12 ON)
If the sensor fails the monitoring test after opening, an alarm is displayed by the blinker lighting up.
Gate closure is not allowed in this condition. Normal operation can be restored only by repairing the
sensor and pressing one of the activated controls.
STOP BUTTON (COM-STOP)
The STOP button stops the gate during any operation.
If held when the gate is fully open (or partially when using the pedestrian control) automatic closing
is temporarily deactivated (if activated by the TCA trimmer and LED DL6 on). It is therefore necessary
to use a new command to make it close.
The automatic closing function is reactivated on the next cycle (if activated by the TCA trimmer and
LED DL6 on).
POWER SENSOR ALARM
The T2 24V control panel has automatic sensors that make the movement of the gate reverse in case
of impact against objects or persons in accordance with the current EN standards (always use the
right tool to ensure compliance with the values imposed by the standard), without special adjustments
on the control panel, as it operates using special internal software. If the power sensor is used in
opening or closing (only in high-speed) and then again, in the opposite direction, the gate stops and
then reverses for 1 second.
The alarm status will be displayed by the blinker which will remain active for one minute, during which
time you can restore gate operation by pressing any command button.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails or remain
engaded for more than 60 seconds, the open, close, k button and pedestrian commands will work
only in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming led.
With the blinking of the programming led, the opening and closing operation are allowed only with
the command button pressed and held. The radio commands and that of automatic closing, will be
excluded, since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard commands that
were selected, such as step by step, automatic mode, radio commands and automatic closing start
functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety strips (or
photocells) the photocells (or safety strips) still work by interrupting the operation in progress.
Note 2: the stop command is not to be considered a safety command that can be bypassed in this
mode. Therefore, when pressed or damaged, it will not allow any movement of the gate.
The dead-man operation is only an emergency operation which must be activated for a very
short period and with the complete installation at sight so to have a secure and safe control
of the system. As soon as possible however, the failing safety devices must be repaired and
activated.
BLINKER
N.B.: This control panel can power ONLY BLINKERS ON A (ACG7061) CIRCUIT with lamps up to 24V
and 20W.
PRE-BLINKING
DIP 5 - OFF => the motor and blinker begin simultaneously.
DIP 5 - ON => the blinker begins 3 seconds before the motor.
GATE OPEN WARNING LIGHT (COM-SIGNAL)
Signals when the gate is open, partially open or not closed completely. Turns off only when the gate
is completely closed. This signal is active during programming. N.B.: Max 3 W. If push buttons or
lamps are in excess, the control panel processes will be endangered and possibly halt operation.
OPERATION AFTER A BLACK-OUT (WITHOUT BATTERIES)
When the power supply comes back the DL1 led turns on and remains on for all the time the gate
stays open. The led will turn off only once the gate is completely closed. It is recommended to fully
open the gate. Let the gate close by itself or with automatic closing, or wait until the blinker stops
flashing before commanding it to close.
This will allow the gate to realign. If, motors were released and moved from the normal position when
closed during the blackout, the first movement after power returns must be complete.
If the black out occurs when the gate is still moving or when the gate is open and the first command
sent after the black out is a closing command, the closing of the gate will be carried out with a total
delay between the two gate leaves. Therefore, first the leaf M2 will close completely; once it is off,
M1 will start closing. This separate movement of the two gate leaves is done to avoid their incorrect
overlapping.
TECHNICAL SPECIFICATIONS
- Temperature range
- Humidity
- Voltage
- Frequency
- Battery power
- Transformer Power
- Maximum absorption
- Network Micro-switches
- Maximum power gate open indicator
34
34
0 ÷ 55°C
<95% without condensation
230V~ ± 10% (120V/60Hz upon request)
50/60 Hz
20-24Vdc
130VA - primary 230Vac - secondary 18Vac
50 mA
100ms
24Vdc 3W (equivalent to one 3W or 5 LED light bulb