General Features
The Floating and ON/OFF Electric Spring Return Actuators are direct-mount, spring,
bidirectional actuators and do not require a damper linkage. The actuators are intended
to be installed on an air damper in HVAC systems.
Figure 1:
Dimensions in mm
(a). Mounting Hole (6 Locations)
(b). Adapter for:
Round spindles: Ø 10...20 mm / Square spindles:
Figure 2:
Side A and B of actuator
Side A: CCW Spring Return Direction
Side B: CW Spring Return Direction
(a). Auxiliary switch adjuster
(b). Pointer showing the position of Actuator
(c). Manual Override
IMPORTANT:
When calculating the torque required to operate dampers, it is
essential to take info account all the data supplied by the damper manufacturer.
Installation and adjustment
Figure 3:
Fitting the Anti-rotation Bracket on the Damper Frame or Duct
(a). M3 x 9.5 mm. Self - Drilling Sheet Metal Screw (Two Locations)
Figure 4:
Changing the position of the coupler
Figure 5:
Allowed shaft lenght
Attach the actuator to the damper spindle by means of the adapter and secure the
locking device with the screws provided.
WARNING:
Do not install or use this Proportional Electric Spring Return
Actuator in or near environments where corrosive substances or vapors
could be present. Exposure of the electric actuator to corrosive
environments may damage the internal components of the device, and
will void the warranty.
Figure 6:
Angle of rotation limiting
(a). Stroke limiting
The actuator is factory set for 90° rotation. Attaching a stroke limiting stop (optional
M9220-603 Adjustable Stop Kit) in the farthest mounting position will reduces the
rotation range of the actuator by 5°. Each progressive mounting position reduces the
rotation range an additional 5° to a maximum of 30° in either end stop position.
Selecting the direction of rotation
Note: For CCW spring return direction, mount the actuator to the damper shaft so that
Side A of the actuator is away from the damper as illustrated in Figure 2. To change the
spring return direction to CW, mount the actuator to the damper shaft so that Side B of
the actuator is away from the damper.
Wiring
WARNING:
The electrical connections for the actuators must be
executed in accordance with the relevant legal requirements.
In order to avoid any personal injury or damage to the equipment or
other property, always isolate the power supply before commencing any
work on the electrical wiring. In order to avoid danger to property, it is
important for the equipment to be used solely for which it is intended.
Wiring Diagrams
WARNING:
The integrated circuits in the actuator are sensitive to static
electricity. Take suitable precautions.
Figure 7:
M9220-AGx-1: Floating Control, Four wire
Figure 8:
M9220-AGx-1: Open / Close, Single Wire Control
Figure 9:
M9220-AGx-1: ON/OFF Control, Two Wire
Figure 10: M9220-BGx-1: ON/OFF Control
Figure 11: M9220-BDx-1: ON/OFF Control
Figure 12: Auxiliary Switch
Auxiliary Switches (xxC Model Only)
WARNING:
Disconnect each of multiple power supplies before making
electrical connections. More than one disconnect may be required to
completely de-energize equipment. Contact with components carrying
hazardous voltage can cause electric shock and may result in severe
personal injury or death.
These models include two integral auxiliary switches, one fixed (S1) and one adjustable
(S2), accessible on either face of the actuator (as illustrated in Fig. 2). The nominal
factory setting for S1 Auxiliary Switch is 11° closing, and the nominal factory setting for
S2 Auxiliary Switch is 81° opening (relative to a 0 to 90° rotation range).
IS_M9220-AGx-1 / M9220-Bxx-1_14-88360-2358_Rev. D_10 2017
The switch point of S2 Auxiliary Switch is independently and continuously adjustable
from 25 to 95°.
Use the method in the following example for the most accurate positioning of
S2 Auxiliary Switch.
1. Move the actuator to the full spring return position.
2. Rotate the switch adjuster until it points to the desired switch point.
3. Connect S2 Auxiliary Switch to a power source or an ohmmeter, and apply power to
the actuator. The actuator moves to the fully open position and holds while power is
applied.
4. Observe the switch point. If required, repeat Steps 2 and 3.
10...20 mm
IMPORTANT:
equipment under normal operating conditions. Where failure or malfunction of the
electric actuator could lead to personal injury or property damage to the controlled
equipment or other property, additional precautions must be designed into the control
system. Incorporate and maintain other devices such as supervisory or alarm system
or safety or limit controls intended to warn of, or protect against, failure or malfunction
on the electric actuator.
Setup and Adjustment
Direction of Action
The Actuators are factory set at DA, 90 degrees of travel. To reverse the rotation, either
move the mode selection switch from Direct Acting (DA) to Reverse Acting (RA),
or reverse the control input wiring to GRY 3 and ORN 4.
Tandem Operation
The tandem configuration provides twice (with two actuators) or triple (with three
actuators) the running and spring return torque of a single actuator.
Two similar actuators can be mounted in tandem using the M9000-158 Tandem
Mounting Kit operate together.
Use two or three actuators from the same model type for tandem operation.
Actuators used in the tandem configuration are wired in parallel.
Note: Manual override does not function after the actuators configured for tandem
operation are mounted to a damper shaft.
Manual Override
Use only the supplied manual override crank to reposition the actuator hub when using
the manual override feature.
1. De-energize the actuator.
2. Insert the hex end of the manual override crank into the manual override adjustment
point on the face of the actuator.
3. Rotate the manual override crank in the direction indicated by the arrow on the label.
4. Rotate the manual override crank a half turn in the opposite direction to lock the
actuator hub in place.
5. To unlock the actuator hub, rotate the manual override crank in the direction indicated
by the arrow on the label. The actuator hub automatically unlocks when power is
applied to the actuator, and returns the actuator to normal drive and spring return
operation.
IMPORTANT:
manual override with a power tool may damage the internal components of the
actuator and cause premature failure. end of travel, the rotational resistance increases;
do not force the actuator hub past this point.
Ordering Codes
Codes
M9220-BGA-1
M9220-BGC-1
M9220-BDA-1
M9220-BDC-1
M9220-AGA-1
M9220-AGC-1
Use the Proportional Electric Spring Return Actuator only to control
Applying excessive torque to the manual override or running the
Descriptions
ON/OFF, 20 Nm, AC/DC 24 V
ON/OFF, 20 Nm, AC/DC 24 V, with 2 auxiliary switches
ON/OFF, 20 Nm, AC 230 V
ON/OFF, 20 Nm, AC 230 V, with 2 auxiliary switches
Floating, 20 Nm, AC/DC 24 V
Floating, 20 Nm, AC/DC 24 V, with 2 auxiliary switches
This document is subject to change without notice