English
Technical Specifications
Product Codes
Power Requirements
- Holding Position
- Holding Position
Transformer Sizing Requirements
- Minimum per Actuator
Input Signal / Adjustments
Auxiliary Switch Rating
Spring Return
Running and Spring Return Torque
Rotation Range
Rotation Time
- Power On (Running)
- Power Off (Spring Returning)
Cycles
Audible Noise Rating
- Power On (Running)
- Power On (Holding)
- Power Off (Spring Returning)
Electrical Connections
(Actuator and Auxiliary Switches)
Conduit Connections
Mechanical Connections
- Standard Shaft Clamp Included with Actuator 12 to 19 mm Diameter Round Shafts, or 10, 12, and 14 mm Square Shafts
- Optional M9220-600 Jackshaft Coupler Kit 19 to 27 mm Diameter Round Shafts, or 16, 18, and 19 mm Square Shafts
Aluminum Enclosure
Ambient Conditions
Shipping Weight
Dimensions
Compliance
- United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for Household and
- Australia and New Zealand C-Tick Mark, Australia / NZ Emissions Compliant
M9220-AGx-1
Floating
AC 24 V (AC 19.2 to 30 V) at 50/60 Hz
Class 2 (North America)
or SELV (Europe)
- Running
15.5 VA
7.7 VA
DC 24 V (DC 21.6 to 26.4 V), Class 2 (North America) or SELV (Europe)
- Running
6.7 W
2.9 W
20 VA
AC 19.2 V to 30 V at 50/60 Hz
or DC 24 V ±10%,
Class 2 (North America)
or SELV (Europe),
500ms minimum pulse width
Two Single-Pole, Double-Throw (SPDT), Double-Insulated Switches with Gold Flash Contacts:
AC 24 V, 50 VA Pilot Duty;
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty
Direction is Selectable with Mounting Position of Actuator:
Side A, Actuator Face Away from Damper for CCW Spring Return;
Side B, Actuator Face Away from Damper for CW Spring Return
20 Nm for a Single Actuator;
40 Nm for Two Like Models
Mounted in Tandem
60 Nm for Three Like Models
Mounted in Tandem
Optional M9220-603 Adjustable Stop Kit
Adjustable from 30 to 90° CW or CCW, Mechanically Limited to 90°
150 Seconds for 0 to 20 Nm
at All Operating Conditions
Independent of Load
20 Seconds for 0 to 20 Nm
at Room Temperature
60,000 Full Stroke Cycles; 1,500,000 repositions
<40 dBA at 1 m
<20 dBA at 1 m
<55 dBA at 1 m
1.2 m Halogen-Free Cable with 18 AWG (0.75 mm
Integral Connectors for 10 mm Flexible Metal Conduit
NEMA 2 (IP54) for All Mounting Orientations
- Operating -40 to 55 °C; 90% RH Maximum, Noncondensing
- Storage -65 to 85 °C; 95% RH Maximum, Noncondensing
See Figure 1
Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators.
- Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic Electrical Controls for
Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment.
- Europe Johnson Controls, declares that these products are in compliance with the essential requirements and other relevant provisions
of the EMC Directive and Low Voltage Directive.
IS_M9220-AGx-1 / M9220-Bxx-1_14-88360-2358_Rev. D_10 2017
M9220-BGx-1
AC 24 V (AC 19.2 to 28.8 V) at 50/60 Hz
Class 2 (North America)
or SELV (Europe)
26 VA
9.3 VA
17.6 W
2.8 W
20 Nm for a Single Actuator;
40 Nm for Two Like Models Mounted in Tandem
24 to 57 Seconds for 0 to 20 Nm at All Operating Conditions
35 Seconds Nominal at Full Rated Load
11 to 15 Seconds for 0 to 20 Nm at Room Temperature
35 Seconds maximum for 0 to 20 Nm at -30 °C
130 Seconds maximum for 0 to 20 Nm at -40 °C
) Wire Leads
2
2.9 kg
This document is subject to change without notice
M9220-BDx-1
ON/OFF
AC 230 V (AC 198 to 264 V) at 50/60 Hz
0.15 A
0.09 A
---
---
---
25 VA
---
<66 dBA at 1 m
<18 dBA at 1 m
<66 dBA at 1 m
3.5 Kg
2