TABLE OF PIPELINE FOR BT 180 DSN - BT 250 DSN
WITH FUEL AT 5° AT 50° C (40° AT THE 5° C PUMPING TEMPERATURE)
Pump axis
SIPHON FEED SYSTEM WITH FEED FROM THE TOP OF THE TANK
Pump axis
Pump axis
TWO STAGE HEAVY OIL BURNER
GRAVITY FEED SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net fi lter
4 Pump
5 Degasifi er
6 Suction pipe
7 Return pipe
8 Automatic fuel interception
device at burner shut off
9 Non-return valve
1 Tank
3 Wire-net fi lter
4 Pump
6 Suction pipe
7 Return pipe
8 Automatic fuel
device at burner shut off
9 One-way valve
10 Bottom valve
SUCTION FEED SYSTEM
1 Tank
3 Wire-net fi lter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
N.B. Comply with existing regulations regarding apparatus required in
the pipeline system
H - Height difference between minimum fuel tank level and pump axis.
L - Total length of pipeline, including vertical lenght. Subtract 0,25 mt.
for every elbow or gate valve.
31 / 80
0006080415 ed2005/08
H
Total length meters
meters
Ø = 1" 1/2
1
35
1,5
40
2
50
2,5
50
interception
H
Total length meters
meters
Ø = 1" 1/2
1
35
1,5
40
2
50
2,5
50
Dimension P = 3,5 m. (max.)
H
Total length meters
meters
Ø = 1" 1/2
0,5
25
1
20
1,5
15
2
10
2,5
5
Øi. 41 mm
35
40
50
50
Øi. 41 mm
35
40
50
50
Øi. 41 mm
25
20
15
10
5