Descargar Imprimir esta página

baltur BT 40 DSN 4T/TD Instrucciones página 35

Publicidad

AUXILIARY PUMP (see BT 8511/6 and BT 8513/7)
In some cases (excessive horizontal distance, vertical distance or high viscosity and always when using the bur-
ners in the dense "D" version) it is necessary to fi t the unit with a "loop" feed system using an auxiliary pump, thus
avoiding direct connection of the burner pump to the tank.
In this case the auxiliary pump can be started as a function of burner start-up and stopped when the burner
stops.
Carry out auxiliary pump electrical connections by connecting the coil (230 V) which controls the pump relay
switch to the "N" terminals (control box input terminal block) and "L1" terminals (downstream from the motor relay
switch).
Always observe the following:
-
the auxiliary pump must be installed as close as possible to the liquid to be sucked.
-
the head must be adequate for the system in question.
-
a fl ow-rate at least equal to burner pump fl ow-rate is recommended.
-
connection piping must be sized as a function of auxiliary pump fl ow-rate.
-
Never electrically connect the auxiliary pump directly to the burner motor relay switch.
TWO STAGE HEAVY OIL BURNER
VISCOSITY - TEMPERATURE CHART
33 / 80
0006080415 ed2005/08

Publicidad

loading

Este manual también es adecuado para:

Bt 50 dsn 4t/tdBt 75 dsn 4t/tdBt 100 dsn 4t/tdBt 120 dsn 4t/tdBt 180 dsn 4t/tdBt 250 dsn 4t/td ... Mostrar todo