Commissioning and operation

7.1

Making and checking presettings

The following presettings need to be made and observed:

Set the bus coupler address(es)

W
Observe Valve address assignment
W
Observe Input/sensor address assignment
W
7.1.1
Set the bus coupler address(es)
The following points must be taken into consideration when
assigning the address(es):
It is not possible to assign addresses twice in the AS-i bus.
W
The bus couplers always have the A and B address in AS-i
W
protocol 2.1.
How to set the bus address(es):
1. Connect the AS-i bus connection (PWR) to an AS-i
addressing device via the addressing cable (see „Spare
parts and accessories" on page 81).
2. Assign the address in the areas 1 to 31.
3. Document the address in the label area of the module and,
if necessary, the cable socket label.
Default setting for all participants: address 0.
Table 8:
Codes for the bus couplers
AS-i...
I/O code
8DI/8DO-AUX
7
4DI/4DO-AUX
7
8DO-AUX
8
4DO-AUX
8
Commissioning and operation
ID code
ID2 code
F
E
F
E
F
E
F
E