2.7 Connection of input/output power cables on UPS terminals
This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connection, check that the battery circuit breaker (19) (see page 8) and that the upstream
protection device (Normal AC source) is open ("0").
Use included insulated ferrules with stranded wires.
8
7
1
3
2
5
4
6
7
1 - Remove the terminal block cover (2
screws) with the included screwdriver.
2 - Insert the Normal AC cable through the
cable gland (8).
3 - Connect the 3 wires to the Normal AC
terminal block.
4 - Insert the output cable through the
cable gland (7).
5 - Connect the 3 wires to the output
terminal block.
6 - Refit the terminal block cover and
tighten the cable glands.
7 - Secure the terminal block cover by
means of 2 screws.
8
7
2. Installation
Always connect first the
earthing wire.
34008030EN/AD - Page 19