Distances Of Safety Devices According To The Standard; Commissioning Checks; Anti Condensation Device Mandatory - Dal Zotto INSERTO IDRO 800 Manual Del Usuario

Tabla de contenido

Publicidad

DISTANCES OF SAFETY DEVICES ACCORDING TO THE STANDARD

The temperature safety sensors must be in place on the machine at a distance no greater than 30 cm from the ow connection. Whenever the
generators lack a device, those missing can be installed on the generator ow pipe, within a distance no greater than 1 m from the machine.

COMMISSIONING CHECKS

Before connecting the boiler:
a) wash all system piping thoroughly in order to remove any residues which might compromise the correct functioning of certain system
components (pumps, valves, etc.).
b) The company recommends installing a magnetic lter in the generator return, to increase the operational life of the boiler, make it easier
to remove impurities and increase the overall e ciency of the system.
It is also advisable to perform an inspection using appropriate instruments, to check for any stray currents that may cause corrosion.
c) check to verify that the ue has adequate draught, that it is not narrowed and that other appliances do not discharge into the ue. This is to
prevent unexpected power increases. The ue tting can be mounted between the boiler and the ue only after this inspection. An inspection
of the connections with pre-existing ues is recommended.

ANTI CONDENSATION DEVICE MANDATORY

Make sure a suitable anti-condensate circuit has been realised, which guarantees an appliance return temperature of at least 55°C. The
automatic thermostatic valve, for instance, is used in solid fuel boilers as it prevents cold water from returning into the exchanger. A high
return temperature allows e ciency improvement, reduces formation of smoke condensation and prolongs the generator's life span. The
manufacturer recommends using the 55°C model with 1" hydraulic connections.
For the products with the *PWM pump control thermostat, installation is considered equivalent to the realisation of a suitable anti-condensate
circuit in the case where::
- the heat generator pump is the only one in the installation, or
- there is a plate heat exchanger between the heat generator and the installation, or
- there is a hydraulic compensator or an inertial storage tank (bu er) between the heat generator and the installation
*Check technical data sheet on website.
Valve on sale as an accessory (optional)
ENGLISH
47

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Natura e calore

Tabla de contenido