N° Terminals
Function
1-2-3
Power supply
4-5-6
Motor 1
7-8-9
Motor 2
10-11
Blinking light
12-13
TLS
14-15
24 Vac
16-17
Lock 12Vdc
18-19
AUX1
20-21
EDGE
22
SWO-M1
23
SWC-M1
24
SWO-M2
25
SWC-M2
26-27
COM
28
Step-by-Step
29
PED
30
OPEN
31
CLOSE
32
PHOT
33
PHOT CLOSE
34
STOP
35-36
Antenna
37-38
AUX2
J3
Radio
The EDGE must be connected exclusively to the special inputs 20/21. Two types of EDGE may be used:
If an edge with resistance 8K2 is used, close the Jumper "DAS".
If a mechanical edge with N.C. contact is used, open the Jumper "DAS".
If the edge is not used, bridge the terminals 20-21 and open the Jumper "DAS".
1) Cut-off power supply.
2) Manually release the wings, move them to approx. half-stroke and lock them again.
3) Reset power supply.
4) Send a step-by-step control signal by pressing the button or the remote control key.
5) The wings should start an opening movement.
If this is not the case, invert the movement wires of the motor. (4<>6 for motor M1, and 7<>9 for motor M2) and the relevant limit
switch inputs (22<>23 for motor M1, and 24<>25 for motor M2).
The programming of the various functions of the control unit is carried out using the LCD display on the control unit and setting the
desired values in the programming menus described below.
The parameters menu allows you to assign a numerical value to a function, in the same way as a regulating trimmer.
The logic menu allows you to activate or deactivate a function, in the same way as setting a dip-switch.
Other special functions follow the parameters and logic menus and may vary depending on the type of control unit or the software
release.
1 – Press the button <PG>, the display goes to the first menu, Parameters "PAR".
2 – With the <+> or <-> button, select the menu you want.
3- Press the button <PG>, the display shows the first function available on the menu.
BRAINY CONTROL UNIT
INPUT/OUTPUT FUNCTIONS
Description
Input 230Vac 50Hz (1-GND/2-Phase/3-Neutral)
Connection of motor 1: (4-start/5-Com/6-start)
Connection of motor 2: (7-start/8-Com/9-start)
Connection of blinking light 230Vac 40W max.
N.O. clean contact for courtesy light, timer, etc.
The activation time is regulated by the parameter TLS
Accessories power supply output 24Vac/1A max.
Accessories power supply output 12Vac/10W for electric lock (16:0V, 17:+12V)
Normally Open clean contact, configurable as SCA- open gate light (default) or photocell test.
Input, sensitive edge contact
Resistive edge: "DAS" Jumper closed
Mechanical edge: "DAS" Jumper open
When the edge is activated, the gate movement is stopped and reversed for about 3s.
OPEN limit switch input motor 1 (N.C contact.)
CLOSE limit switch input motor 1 (N.C. contact)
OPEN limit switch input motor 2 (N.C. contact)
CLOSE limit switch input motor 2 (N.C. contact)
Common for limit switch and all the control inputs.
Step-by-Step button input (N.O. contact)
Pedestrian button input (N.O. contact)
OPEN button input (N.O. contact), configurable as Clock contact
CLOSE button input (N.O. contact)
Active photocell input on opening and closing
Active photocell input only on closing
STOP button input (N.C. contact)
Antenna connection for plug-in radio receiver board (35-screen/36-signal).
Voltage-free Normally Open Contact. Configurable as second radio channel (default) or SCA-
open gate LED.
Plug-in connector for radio receiver.
NOTES
TO ChECK CONNECTIONS:
PROGRAmmING
TO ACCESS PROGRAmmING