Set-point reduction percentage
Type of external analogue signal
Twin operating mode
Pump start control

Table 7: Factory settings

14. TYPES OF ALARM

Alarm Code
Alarm Symbol
 
e0 - e16; e21
e17 - e19
e20
 
e22 - e31
e32 - e35
 
e37
e38
e39 - e40
 
e43; e44; e45; e54
 
e46
e42
 
 
e56
 
e57
e58
Tabella 8: Elenco allarmi
50 %
0-10V
 
= Alternate every 24h
EXT (from remote signal on input IN1).
Alarm Description
Internal Error
 
Short Circuit
Voltage Error
 
Internal Error
Electronic system excess temperature
Low voltage
 
High voltage
 
Pump blocked
Pressure Sensor
 
Pump Disconnected
Dry operation
Motor excess temperature (motor
protector trips)
Frequency of PWM external signal less
than 100 Hz
Frequency of PWM external signal
 
greater than 5 kHz
15. DISPOSAL
This product or any part of it must be disposed of correctly:
- Use public or private local systems for waste collection.
- If that is not possible, contact Dab Pumps or the nearest authorised
service workshop.
INFORMATION
Frequently asked questions (faq) on the ecodesign directive 2009/125/
ec establishing a framework for the setting of ecodesign requirements
for energy-related products and its implementing regulations: http://
ec.europa.eu/enterprise/policies/sustainable-business/documents/
eco-design/guidance/files/20110429_faq_en.pdf
Guidelines accompanying commission regulations implementing the
ecodesign directive: http://ec.europa.eu/energy/efficiency/ecodesign/
legislation_en.htm - see "circulators"

16. ERROR CONDITION AND RESET

Display
indica-
Description
tion
 
Internal
e0 – e16
error
Low mains
e37
 
voltage
(LP)
High mains
 
e38
voltage
(HP)
ENGLISH
Reset
- Switch off system power.
- Wait for the warning lights on the control panel
to go off, then power the system again.
- If the error persists, change the circulator.
- Switch off system power.
- Wait for the warning lights on the control panel
to go off, then power the system again.
- Check that the mains voltage is correct, if nec-
essary reset it at the plate values
- Switch off system power.
- Wait for the warning lights on the control panel
to go off, then power the system again.
- Check that the mains voltage is correct, if nec-
essary reset it at the plate values.
GB
35