- Before installing the circulator, accurately flush the system with only wa-
ter at 80°C. Then drain the system completely to eliminate any harmful
substance that may have got into circulation.
- Assemble in such a way as to avoid dripping on the motor and on the
electronic control device during both installation and maintenance.
- Avoid mixing additives derived from hydrocarbons and aromatic prod-
ucts with the circulating water. It is recommended that the addition of
antifreeze, where necessary, should not exceed 30%.
- In the event of heat insulation use the special kit (if provided) and en-
sure that the condensate draining holes in the motor casing are not
closed or partly blocked.
- To guarantee maximum efficiency of the system and long life of the
circulator it is recommended to use magnetic sludge-removing filters to
separate and collect any impurities present in the system (particles of
sand, particles of iron and sludge)
Never insulate the electronic control device.
- In the case of maintenance, always use a set of new gaskets.

7.2 Rotation of the Motor Heads

If the circulator is installed on pipes in a horizontal position, it will be nec-
essary to rotate the motor with the respective electronic device through
90 degrees in order to maintain the grade of IP protection and to allow
the user a more convenient interaction with the graphic interface (see
Figure 2).
Before rotating the circulator, ensure that it has been completely
drained.
Should it be necessary to rotate the motor heads, follow the instructions
below with care to ensure correct installation:
Unscrew the 4 screws fixing the motor assembly to the pump body
1.
(figure A).
2.
2. Rotate the motor assembly keeping it in the seat where it cou-
ples with the pump body (figure A-B).
3.
Once the head has been rotated into the desired position, tighten
the 4 screws, always proceeding in cross formation (figure C).
If the motor assembly has been removed from its seat, pay the greatest
attention during assembly, taking care to insert the impeller completely
in the floating ring before tightening the retaining screws (figure D). If it
has been correctly assembled, the motor assembly rests completely on
the pump body.
Incorrect assembly may damage the impeller, causing a typical
rubbing noise when the circulator starts.
2
1
A
1
Torque: 19-20
Nm
3
C
Figure 2: Instructions for motor head assembly
The electronic control device must always remain in vertical po-
sition!
ENGLISH
3
B
4
2
D
GB
25

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Evoplus b 120/220.32 san mEvoplus d 120/220.32 mEvoplus b 40/220.40 mEvoplus b 60/220.40 mEvoplus b 80/220.40 mEvoplus b 100/220.40 m ... Mostrar todo

Tabla de contenido