Baxi CBP Matic 18 Manual De Instrucciones página 211

Caldera de pellets
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

- If the light do not go out when moving the sensor away from the pellets or do not
come on when approaching, re-adjust the sensitivity of the sensor and repeat the
test.
- You shall perform the sensitivity adjustment for both the boiler's tank level sensors
and for the storage unit's level sensor.
You can also adjust the sensor's response time, to set the time the sensor waits
before sending the signal to the circuit board upon detecting the pellets. This setting
can be made directly on the storage unit electronic circuit board, on the upper right
corner, using the same procedure used for adjusting the sensitivity – rotate clockwise
to increase the response time and counter clockwise to decrease the response time.
The response time should be set to the minimum value
Installing the storage unit on the right side of the boiler
The level sensor of the storage unit must always be installed on the side closest to
the boiler.
1 – If you want to install the storage unit on the right side of the boiler you must install
the level sensor on the left side of the storage unit, in the same place where he
comes assembled by default. Before, you should disconnect the plug of the cable
connected to the circuit board, to facilitate the assembly. To fasten it, you should use
the screws previously removed, and put it in the position shown in Figura 29-b.
a)
Figure 28 – Adjustment of the sensors sensitivity
b)
48

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Cbp matic 24Cbp matic 30

Tabla de contenido