2 - STORAGE

• Store the units in a dry room protected from the weath-
er and maintained at a temperature of between +5°C and
+60°C. Make sure that they do not touch any walls or each
other or are in direct contact with the floor. Protect them
from impacts and make sure that nothing is placed on them.
• The heat exchangers must be placed on blocks that have
been adjusted to ensure adequate stability and levelness.
The floor must be protected from caving in.
• Do not remove the seals on the ends of the pipes until you
are ready to make the hydraulic connections.
• All unused spare parts must be stored away from damp,
light, and dust, and protected from impacts.
• Gaskets and gasketed plates must be stored in a cardboard
box at a temperature of between 10°C and 30°C. Maximum
shelf life: 6 to 12 months.

3 - INSTALLATION

Always read this guide carefully before working on the
unit and keep it in a safe place for future reference.

3.1 - Choice of location

The intended location of the unit should be fully accessible so
as to ease servicing and maintenance operations and allow
easy removal of the plates from the side of the unit (Fig. 3).
Adequate clearance must be left in front of the safety and
10
control devices.
A
Fig. 3

3.2 - Installation recommendations

• CARRIER plate heat exchangers have a limited operating
pressure and temperature range. Install all the necessary
safety devices to prevent overrunning the limits specified
on the order documents. Approval to use the plate heat ex-
changers at higher conditions must be obtained from CAR-
RIER. It is recommended to fit pressure and temperature
test points near the unit.
• Make sure that the heat exchanger is compliant with the
safety rules in force on the site of use (explosive atmos-
phere, etc.).
• Install burn hazard signs wherever the surface temperature
of pipes exceeds 60°C.
minimum recommended
value (mm)
Model
A
DN32
700
DN50
1000
DN65
1000
DN100
1500
DN150
1500
DN200
2000