TROUBLESHOOTING/SERVICE/SMARTWARRANTY™

The key thing to remember when servicing the SmartZone™ controller
is DO NOT REMOVE THE ENTIRE CONTROLLER FROM THE
SITE. SmartZone™ controllers are warranted by component for ease
of service, repair and warranty.
The SmartWarranty™ is valid on components only. Those
components are the front panel, the mother board, the PLUS4 board,
and the buffer board. The SmartWarranty™ covers defects in
materials, workmanship, and damage resulting from indirect lightning,
provided the controller was installed and grounded properly.
Each of the above components will have its own date code. The
SmartWarranty™ will be in effect for two years from that date code.
Defective components under warranty must be returned to Nelson.
Replacement of components will be delivered to the distributor within
72 hours of receipt of the defective components – guaranteed! (For
more information on the Nelson Warranty, see page 13).
SYMPTOM
controller counts down, but does not irrigate
no output to zone, pump or master valve
no AC and blank display (no low bat. was
displayed)
LCD is blank
zone does not come on with manual operation
cycle does not begin at set start time
E2 error displayed that does not clear after
reset
E1 error displayed that does not clear after
reset
display does not show correct number of
zones
no zones after 20 work
display will not show more than 20 zones
POSSIBLE CAUSE
• controller is in Off mode
• blown fuse or circuit breaker
• AC disconnected
• PLUS4 board for that block of four has failed
• no battery or dead battery
• no AC and no battery
• ribbon cable is installed wrong or
disconnected
• controller is off
• a sensor has suspended watering
• current time is incorrect
• today is not a watering day
• another start time is set for the same time so
one has been delayed until the other is
finished
• was running a manual cycle at time of start
• front panel has failed
• mother board has failed
• PLUS4 board has failed
• no AC Power
• buffer board (metal box only) has failed
or 4th PLUS4 board
SOLUTION
• press the Off/On/Sensor Override button
until the arrow is across from On
• check fuse or circuit breaker
• check AC source, unit should work from
battery, but with E5 error in the On position
• replace PLUS4 board
• replace battery and press reset (voltage level
is only checked when you lose AC)
• install battery to regain use of display, check
AC to ensure output to field
• ensure ribbon cable between the front panel
and controller board is connected at both
ends red stripe up (no. 1 position)
• press Off/On/Sensor Override button until the
arrow is across from On
• wait for sensor to dry out or press
Off/On/Sensor Override until the arrow is
across from Sensor Override
• correct current time
• select program letter review schedule
• change the start times so they do not overlap
• programmed start time will be stacked and
run, but not until after manual operation is
complete
• replace front panel
• replace mother board
• replace appropriate PLUS4 board
• without power, only 8 zones will show on LCD
• replace buffer board
swap PLUS4 boards
11