en-US
6.5.5.1
Direct start-up
6.5.5.2
Star-delta activation
6.5.5.3
Soft starter
6.5.6
Operation with frequency con-
verter
7

Commissioning

7.1

Personnel qualifications

7.2

Operator's obligations

7.3

Rotation control

30
Commissioning
At full load, set the motor protection switch to the rated current (see rating plate). At partial
load, it is recommended to set the motor protection switch to 5 % above the measured cur-
rent in the duty point.
The motor protection setting depends on the installation:
▪ Motor protection installed in the motor line: Set the motor protection to 0.58 x the rated
current.
▪ Motor protection installed in the power supply cable: Set the motor protection to the rated
current.
The maximum start-up time in star connection is 3 seconds.
At full load, set the motor protection switch to the rated current (see rating plate). At partial
load, it is recommended to set the motor protection switch to 5 % above the measured cur-
rent in the duty point. Furthermore, observe the following points:
▪ Current consumption must always be lower than the rated current.
▪ Complete starting and stopping within 30 s.
▪ To avoid power dissipation, bypass the electronic starter (soft start) once normal operation
is reached.
Operation on the frequency converter is permitted. Refer to the appendix for the relevant
requirements!
WARNING
Hand and foot injuries due to a lack of protective equipment!
During work there is a risk of (serious) injury. Wear the following protective equipment:
• Safety gloves that protect against cuts
• Safety shoes
• If lifting equipment is used, a protective helmet must also be worn.
▪ Electrical work: A qualified electrician must carry out the electrical work.
▪ Operation/control: Operating personnel must be trained in the operating principle of the
complete system.
▪ Provide installation and operating instructions by the mixer or at a place specially reserved
for it.
▪ Make the installation and operating instructions available in a language the personnel can
understand.
▪ Make sure that the installation and operating instructions are read and understood by all
personnel.
▪ All safety devices and emergency cut-outs on the system-side must be active and checked
to ensure that they work properly.
▪ The mixer is suitable for use under the specified operating conditions.
The mixer is checked at the factory and set to the correct direction of rotation for a clock-
wise rotating field. The connection is made according to the information in the "Electrical
connection" section.