6
Wiring the device
Power terminals
Devices in the range 145 ... 245 A (75 ... 130 kW)
Mains
Terminal X100
B
A
C
C
C
Terminal data
Terminal 0
Device size 81
Device size 82
Threaded bolt 1
Terminal data
Terminal PE
106
Labelling
Description
L1
Connection of the mains phases L1, L2, L3.
0: Terminal (scope of supply); conductor connection with wire end
L2
ferrule
L3
1: Threaded bolt M10 (at the device)
2: Ring cable lug for M10 (not included in the scope of supply)
D
3: Sleeve (scope of supply)
Wiring:
Standard: With terminal 0 and wire end ferrule
Variant: With ring cable lug 2 for threaded bolt M10 1
(remove terminal 0 first). In case of a double assignment, use the
sleeve 3 from the scope of supply.
SSP94KLB
Max. conductor cross−section
2
[mm
]
150
300 mcm
240
500 mcm
−
Labelling
Description
PE
Connection for the PE conductor on the supply side
SSP94KL0X8
Max. conductor cross−section
2
[mm
]
70
l
Tightening torque
[AWG]
[Nm]
42
56
−
25
Tightening torque
[AWG]
[Nm]
2/0
10
!
[lb−in]
375
Inbus 8
500
Inbus 10
221
SW17
!
[lb−in]
88
SW13
EDK94SH366 DE/EN/FR/ES/IT 7.0