Wiring the device
Power terminals
Device 292 A (150 kW)
Shield plate mounting (optional)
In order to provide for the secure support of cable shields, we recommend mounting the
shield plate 0 from the scope of supply.
How to proceed:
1. Remove screws:
4 x TX25 1 (fastening of shield plate)
3 x SW13 2 (PE connection)
2. Lead the shield plate 0 through the slot in the base of the device.
3. Securely mount the shield plate 0 with 4 screws 1.
4. Screw in three screws 2 for PE support that is to be installed later.
Fig. 6−5
112
Shield sheet installation