Operating Conditions - Lenze L-force Drives 9400 E94BSHE Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4
Technical data
General data and operating conditions
Mounting conditions
Mounting place
Mounting position
Clearance
above/beneath
at the side
Supply conditions "Single Drive"
Power systems
TT
TN
IT
Motors

Operating conditions

Environmental conditions
Climate
Storage
Transport
Operation
Site altitude
Pollution
Vibration resistance
Operation
90
EN 60034
IEC/EN 60721−3−1
IEC/EN 60721−3−2
IEC/EN 60721−3−3
EN 61800−5−1
2
(9.81 m/s
= 1 g)
German Lloyd
IEC/EN 60068−2−6
l
in the control cabinet
vertical
Comply with the device−relating mounting instructions.
Can be installed in a row without any clearance
Operation allowed without restrictions.
Up to device size 83: additional measure necessary inside
device (see "Earthing of internal EMC filter", ^ 99)
device size 91: Specify when ordering
Only use motors that are suitable for inverter operation.
Insulation strength: max. û ³ 1.5 kV, max. du/dt ³ 5 kV/ms
1K3 (−25 ... +60 °C)
2K3 (−25 ... +70 °C)
3K3 (−10 ... +55 °C)
Current derating of +45 ... +55 °C: 1 %/°C
0 ... 4000 m amsl
In the case of 1000 ... 4000 m amsl: current derating
10 %/1000 m
Degree of pollution 2
5 ... 13.2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration−proof up to 0.7 g
Device size 81 ... 83: On the customer's premises, mounting
must be carried out with vibration dampers. Please consult
Lenze.
Device size 91: The control cabinet must be
vibration−damped.
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration−proof up to 1 g
EDK94SH366 DE/EN/FR/ES/IT 7.0

Publicidad

Tabla de contenido
loading

Tabla de contenido