4.2.2. Special cases which may occur during the tests "MAN" & "TIMER"
In case a value of R
R
was detected (depending on the
MAX
selected voltage see following Note
table, the instrument emits a double
beep at the end of the test indicating
the positive outcome of the test and
displays a screen similar to the screen
alongside.
Maximum resistance value that can be measured
(999Ω is displayed if a rated voltage of 500V was
selected see table).
In case a test is performed at a voltage
lower than the set rated voltage, at
the end of the test the instrument emits
a long beep and displays a screen
similar to the screen alongside.
ATTENTION: the test of resistance R
performed at a voltage value lower than the set
rated voltage. Low insulation case. This case
occurs under low insulation conditions or in the
presence of capacitance on the installation.
SAVE
SAVING:
If the terminal voltage is greater than
30V, the instrument does not perform
the test, displays the screen alongside
for 5 seconds after which, it shows the
default screen relative to the R
under selected mode.
SAVE
THIS RESULT CANNOT BE SAVED.
greater than
ISO
was
ISO
The test can be stored pressing the SAVE key twice (refer to
paragraph 5.1).
test
ISO
R
ISO
> 999
MΩ
500 V
20
s
MAN
R
ISO
ν0.01
MΩ
500 V
20
s
MAN
R
ISO
ν 33V
VOL
AG
The symbol ">"
means that the
resistance value
R
is greater
ISO
than R
MAX
Test duration
Selected mode
MAN
Selected mode
MAN
ATTENTION: the
test was not
carried out.
Check that the
circuit is not
energized.