SICK Stsndart IN4000 Instrucciones De Servicio página 70

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Chapter 3
Tab. 6: Electrical
output para-
meters for the
IN4000
Standard
safety switches
WARNING
70
Product description
Logical "1"
Logical "0"
If the actuating element is outside the enable zone,
the output is switched off (Logical "0"; safe state).
Different timing behaviour, including continuous
Logical "1" is indicative of an error.
Cross-circuits are detected by the safety switch and
result in an error message (continuous Logical "1").
The pull-down current for the source of the PSDI
must not exceed 30 mA, as the safety switch cannot
process this current. It is then not possible to
provide an error message.
© SICK AG • Industrial Safety Systems • Germany • Subject to change without notice • 8010934/YTC9/2016-04-01
≥ 15 V
2 ... 15 mA
≥ 11 V
15 ... 30 mA
Output impedance typ.
27 Ohm
5V
Residual current 0 mA
Pull-down current typ.:
IN40-D0101K: 50 mA
IN40-D03 ..: 30 mA
IN40-D0202K: 30 mA