Connection And Adjustment; Electrical Connection - SICK Stsndart IN4000 Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Operating Instructions
IN4000 Standard
5

Connection and adjustment

WARNING
© SICK AG • Industrial Safety Systems • Germany • Subject to change without notice • 8010934/YTC9/2016-04-01
Connection and adjustment
Electrical
5.1
The supply voltage (L+...L–) is to be connected
between Pin 1 and Pin 3 on the plug. The nominal
voltage is 24 V DC. This voltage is allowed, as per
EN 61 131-2, to fluctuate between 19.2 V and 30 V
with 5 % residual ripple.
The supply voltage must comply with SELV as per
EN 60 950-1.
For application and usage as per the requirements of
cULus, the supply voltage must be provided by a trans-
former with protected secondary. A safe industrial
power supply unit with overcurrent protection is to be
used. In case of error 60 V DC may not be exceeded.
The following applies to cuboid sensors:
Cable diameter control
circuit
AWG
(mm²)
26
(0.13)
24
(0.20)
22
(0.32)
20
(0.52)
18
(0.82)
16
(1.3)
connection
Overcurrent protection
Maximum load of the protective
Chapter 5
device
Ampere
1
2
3
5
7
10
81

Publicidad

Tabla de contenido
loading

Tabla de contenido