Funciones de PROFIBUS DP-V1
I
10
Planificación del proyecto de un maestro C1
0 0
10.4.3 Datos técnicos DP-V1 para puerta de acceso del bus de campo UFF41B
114
•
Comentario sobre el componente funcional:
Write service: x2h, fixed setpoint: P160, index 8489d = 2129h
Wiring of FB:
"Drive_IO_Address": (INT)
"bService":
(BYTE) Read: 01h;
"bAxis":
(BYTE) Sub address/SBUS address of lower-level MC07
"wParameterindex":
(WORD) Parameter index => "MC07 Communication" manual
"wSubIndex":
(WORD) MOVILINK subindex = 0
"dwWriteData":
(DWORD) Parameter data for WRITE service
"InstanzDB_SFB52(BLOCK_DB) Instance DB for the SFB52
"InstanzDB_SFB53(BLOCK_DB) Instance DB for the SFB53
"fActivate"
(BOOL) Activation bit
"fBusy":
(BOOL) Parameter service is active
"fDone":
(BOOL) Parameter service was executed
"bError"
(BYTE) No error = 0; S7 error = 1; TimeOut = 2;
"dwData":
(DWORD)bError = 0 => Parameter value after READ service
Archivo GSD para DP-V1:
Nombre del módulo para la planificación del proyecto:
Número de conexiones C2 paralelas:
Registro de datos compatible:
Número de ranura compatible:
Código de fabricante:
Profile-ID:
C2-Response-Timeout:
Longitud máx. del canal C1:
Longitud máx. del canal C2:
Manual – Puerta de acceso del bus de campo UFF41B DeviceNet y PROFIBUS DP
Input address of the process data =>Hardware config.
Write 02h,
volatile writing 03h
MOVILINK error = 3
bError = 1 => S7 error code
SEW_600D.GSD
Adv. Gateway UFF
2
Índice 47
Recomendado: 0
10A hex (SEW-EURODRIVE)
3A
1 s
240 bytes
240 bytes
65377AEN