2.5
Fault and anomaly signalling.
The Victrix 24 kW boiler indicates any malfunctions using a code shown
ES
on the boiler display (1).
In case of malfunction or anomaly the problem is indicated by flashing of
the symbol (
) and light-up of the relative error code:
PL
Anomaly signalled
TR
No power block, parassite flame
Safety thermostat block (overtemperature), exhaust ther-
mostat or flame control anomaly
CZ
Delivery sensor anomaly
Domestic sensor anomaly
Reset selector broken
SI
Calibration function on (displayed on RFC)
System pressure too low
HU
Configuration error
Fan anomaly
Parasite flame block
RU
Insufficient circulation
Remote control communication loss
Low power supply voltage
IE
N.B.: on the Remote Friend Control (Optional) the error code corresponds
to the preceding list with the letter "E" in front (e.g. code 01 RFC code
E01).
SK
Ignition block. The boiler lights up with each demand for room heating or
hot water production. If this does not occur within 10 seconds, the boiler
goes on "ignition block" (code 01). To eliminate the "ignition block", turn
the main selector (2) temporarily to the Reset position. On first ignition
or following a prolonged downtime the "ignition failure" signal may have
to be inhibited. If this phenomenon occurs frequently, contact a qualified
technician for assistance (e.g. Immergas Technical Services Centre).
Overtemperature block. During operation, if a fault causes excessive
overheating internally, in the exhaust, or an anomaly occurs in the flame
control section, an overtemperature block is triggered in the boiler (code
02). To eliminate the "overtemperature block", turn the main selector (2)
temporarily to the Reset position. If this phenomenon occurs frequently,
contact a qualified technician for assistance (e.g. Immergas Technical
Services Centre).
System delivery sensor anomaly. If the board detects an anomaly on the
system delivery NTC sensor (code 05) the boiler will not start; contact
a qualified technician for assistance (e.g. Immergas Technical Services
Centre).
Domestic sensor anomaly. If the board detects an anomaly on the domestic
system NTC sensor (code 06) the boiler will signal the anomaly. In this case
the boiler will continue to produce domestic hot water, but performance
levels will not be optimum. Also, in this case the antifreeze function is
disabled and it is therefore necessary to contact a qualified technician (e.g.
from the Immergas Service centre).
Reset selector broken. If the selector (2) stays at Reset for more than 30
seconds, due to a malfunction, the boiler will signal an anomaly (code
08). Turn the boiler off and then on again. If the anomaly is still signalled
even when the boiler is turned on again, contact a qualified technician for
assistance (e.g. Immergas Technical Services Centre).
System pressure too low. The water pressure sensed within the heating
circuit is insufficient to guarantee proper operation of the boiler. Make
sure the pressure in the system is between 1÷1.2 bar. If normal conditions
are restored the boiler restarts without having to be reset. If this anomaly
persists, contact a qualified technician for assistance (e.g. Immergas Techni-
cal Assistance Service).
Configuration error. If the card detects an anomaly or an inconsistency
on the electrical wiring, the boiler will not start. If normal conditions are
restored, the boiler starts without having to be reset. If the anomaly persists
contact a qualified technician (e.g. Immergas After-Sales Service).
196
Fan anomaly. This occurs if there is a mechanical or electronic malfunction
in the fan. Try turning the boiler off and then on again. If this anomaly
persists, contact a qualified technician for assistance (e.g. Immergas Techni-
cal Assistance Service).
Parasite flame block. This occurs in case of a leak on the detection circuit
or anomaly in the flame control unit. It is possible to reset the boiler to allow
a new attempt at ignition. If the boiler does not start, contact a qualified
Error
technician (e.g. Immergas After-Sales Service).
code
Insufficient water circulating. This occurs if there is overheating in the
01
boiler due to insufficient water circulating in the primary circuit; the
causes can be:
02
- low circulation; check that no shutoff devices are closed on the heating
05
circuit and that the system is free of air (deaerated);
06
- circulating pump blocked; free the circulating pump.
08
If this phenomenon occurs frequently, contact a qualified technician for
assistance (e.g. Immergas Technical Services Centre).
09
Remote control communication loss. This occurs if an uncompatible
10
remote control is connected, or if communication between the boiler and
15
the Remote Friend Control is lost. Try the connection procedure again by
turning the boiler off and turning the selector (2) to (
16
is still not detected on re-starting the boiler will switch to local operating
20
mode, i.e. using the controls on the boiler itself. If this phenomenon oc-
curs frequently, contact a qualified technician for assistance (e.g. Immergas
27
Technical Services Centre).
31
Low power supply voltage. This occurs if the power supply voltage is
37
lower than the allowed limits for correct boiler functioning. If normal
conditions are restored, the boiler starts without having to be reset. If
the phenomenon occurs frequently, contact a qualified technician (e.g.
Immergas After-Sales Service).
Signalling and diagnostics - Display on Remote Friend Control screen
(optional). During normal boiler operation the room temperature value
is displayed on the Remote Friend Control screen; in case of malfunction
or anomaly, the temperature is replaced by the relative error code given in
the table above.
Important: if the boiler is set to stand-by "
not powered, which means that all the programs stored will be lost if the
batteries run out.
2.6
Boiler shutdown.
Turn the main selector (2) to "
the appliance.
Never leave the boiler switched on if left unused for prolonged periods.
2.7
Restoring heating system pressure.
Periodically check the system water pressure.
The boiler pressure gauge should read a pressure between 1 and 1.2 bar.
If the pressure falls below 1 bar (with the circuit cool) restore normal pressure
via the valve located at the bottom of the boiler (see figure).
N.B.: close the valve afterwards.
If pressure values reach around 3 bar the safety valve may be activated.
In this case contact a professional technician for assistance.
In the event of frequent pressure drops, contact qualified personnel for
assistance to eliminate the possible system leakage.
). If the RFC
". The remote control is
" and turn off the gas tap upstream of