TECHNICIAN - INITIAL BOILER CHECK
ES
To start up the boiler, proceed as follows:
- ensure that the declaration of conformity of installation is supplied with
the appliance;
PL
- ensure that the type of gas used corresponds to boiler settings;
- check connection to a 230V-50Hz power mains, correct L-N polarity
and the earthing connection;
TR
- switch on the boiler and ensure correct ignition;
- check the domestic and heating ∆p gas values;
- check the CO
in the fumes at max. and min. output;
2
CZ
- ensure activation of the safety device in the event of gas supply failure,
as well as the relative activation time;
- check activation of the main circuit-breaker switch upstream of the boiler
SI
and on the unit;
HU
3.1
Wiring diagram - Victrix 24 kW.
RU
IE
SK
ZONES BOARD
(Optional)
Key:
A4 - Display card
B1 - Delivery sensor
B2 - Domestic circuit sensor
B3 - External sensor (optional)
CAR - Remote Friend Control (optional)
E1 - Ignition plugs
E2 - Igniter sensor
E4 - Safety thermostat
E6 - Fumes thermostat
G2 - Igniter
M1 - Boiler circulating pump
M20 - Fan
Remote Friend Control: the boiler is designed to use the Remote Friend
Control (RFC), which must be connected by means of terminals 42 and
43 on the terminal board (located under the sealed chamber), respecting
the polarity and eliminating jumper X40.
198
Black
- check that the intake and/or exhaust terminals are not blocked;
- ensure activation of all regulation devices;
- seal the gas flow rate regulation devices (if settings are modified);
- ensure production of hot domestic water;
- ensure sealing efficiency of water circuits;
- check ventilation and/or aeration of the installation room where pro-
vided.
If any checks/inspection give negative results, do not start the boiler.
Supply
Antifreeze
230 Vac
kit
50 Hz
Orange
Orange
No.
FAN REVS
Optional kit
ONE RELAY
BOARD
M30 - 3-way valve
S2 - Mode selector
S4 - Domestic circuit flow switch
S5 - System pressure switch
S7 - Heating timer selector
S9 - Domestic hot water mode selector switch
S10 - Circulating mode selector
S13 - Heating temperature range selector
S20 - Room thermostat (optional)
T2 - Low voltage transformer
U1 - Rectifier inside the gas valve connector
X40 - Room thermostat jumper
Y1 - Gas valve
Room thermostat: the boiler is designed to use the Room Thermostat (S20),
which must be connected by means of terminals 40 - 41 on the terminal
board (located under the sealed chamber), respecting the polarity and
eliminating jumper X40.
X19 used for connection to personal computer in maintenance opera-
tions.
X17 used to update software.
Brown
Blue
Orange
Red
Black