State Of The Circuits - Hitecsa Advance EQS Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

EXP or PdC+RC100 versions
Indicates that power absorption optimisation action is active
[OPTIMIZER ON]
Indicates that the Force Noise Reduction function is active
[FNR ON]
** Evaporator inlet water temperature
Prim.
*** Evaporator output water temperature
** Recovery inlet water temp
ec.
*** Recovery outlet water temp
*** Disposal unit outlet water temperature
Smal.
(for water-water units only)
ON
OFF by alarm (the machine is Off due to the presence of an
alarm)
OFF by superv. (the machine is placed at Off by an outside
supervisor)
OFF by seq. (the machine is set Off due to a decision of the
unit's sequencer)
Status
OFF by timer (the machine is Off by time periods)
Off by SCR (the machine is Off by digital input)
OFF from display (the machine is placed at Off by manual
setting)
Disabled (the machine is kept off for the time necessary to
heat the compressor crankcase oil)
Off by T.Est. (the machine is OFF due to the low external
air temperature)
Pre-circulation phase of a pump (primary or recovery)
[PRECIRC]
Indicates operating mode of the machine:
Automatic (primary cooling and/or recovery heating)
Mode
Select (primary cooling and/or recovery heating)
Defrost (if the unit is defrosted)
defrost. parz. (in case of defrost of a single circuit)
Allows switching the unit on/off
ON = Unit ON
On/Off display
OFF = Unit OFF
EXP and PdC+RC100 versions
It displays the primary or recovery set-point status
Setpoint
Input water temperature primary or recovery
Inlet
Disposer input water temperature (°C). Transducer pressure
Outlet
(bar).
Indication of the adjustment temperature used.
REG
ON
OFF by alarm (the machine is Off due to the presence of an
alarm)
OFF by superv. (the machine is placed at Off by an outside
supervisor)
OFF by seq. (the machine is set Off due to a decision of the
unit's sequencer)
OFF by timer (the machine is Off by time periods)
Status
Off by SCR (the machine is Off by digital input)
OFF from display (the machine is placed at Off by manual
setting)
Disabled (the side is excluded by manual setting)
Off by T.Est. (the machine is OFF due to the low external air
temperature)
Waiting phase for pause time, if primary pump and / or
[PAUSE]
recovery on request
Indicates operating mode of the machine:
Automatic (primary cooling and/or recovery heating)
Mode
Select (primary cooling and/or recovery heating)
Defrost (if the unit is defrosted)
defrost. parz. (in case of defrost of a single circuit)
USM_CONTROL EQS_2335a21275_208549_210701_ES-EN-FR-DE-IT
Primary control may be enabled or disabled.
If primary is disabled the unit no longer produces cooling or
Enables the
heating on the primary side (the primary side pump also
primary
switches off unless the anti-freeze alarm is triggered). This
default parameter is SI (YES) (primary enabled).
Recovery control may be enabled or disabled
If recovery is disabled the unit no longer produces cooling or
Enables
heating on the recovery side (the recovery side pump also
recovery
switches off unless the anti-freeze alarm is triggered). This
default parameter is YES (recovery enabled).
I.2.2

State of the circuits

Pressing the UP and DOWN keys, from the main screen it is possible to scroll
some menus that allow to control the state of the unit and some settings. The first
screen to be displayed is the cooling state of circuit 1 and then the other circuits (if
more than one).
Screen code. The letter indicates the menu, while the
1
number is progressive
(only for EXP and HP+RC100 versions)
Circuit off
[N]
Cooling circuit
[F]
Recovery unit side hot circuit
[R]
[F+R]
Cooling+recovery circuit
Primary side hot circuit
[P]
2
Circuit in defrost cycle on the main exchanger
[D]
Circuit in defrost cycle on the secondary exchanger
[SD]
(only chiller versions with RC100) Circuit in hot
[REC]
production on recovery side
(DS option only) Circuit in hot production on
DS
desuperheater side
Display of the pressure [barg]
3
AP
Display of the high pressure value switching into
4
temperature [°C]
Display low pressure [barg]
5
BP
Display of the low pressure value switching into
6
temperature [°C]
Display of the electronic thermostatic valve positioning [n°
STEPS
opening step
7
Display of the refrigerant level valve positioning [%]
FLOOD
Display of the compressor intake temperature.
Ta
(Only with Turbocor compressor)
8
LBV1/LBV2
Display of the position of the bypass valve of compressor
LBV/LBV1+2
1, 2 or both of the circuit
Display of the overheating value [K]
SH
Display of the refrigerant level in the flooded heat
9
FLOOD
exchanger [%]
Display of the subcooling value [K]
SC
Analogue signal steps and percentage of the fan speed
3 80%
adjustment (only water-air units)
10
Display of the adjustment speed (only water-water unit)
Pump: 80%
65
CONTROL EQS