II.2.2
MANAGEMENT OF COMPRESSOR
PARTIALISATION SOLENOID VALVES
Bitzer compressors
Regulation of four step standard power
CR1
CR2
Load
NO2
NO3
NO8
NO9
Off
Off
100%
Off
75%
On
Off
50%
On
Off
Off
25%
Solenoid energised
On
Solenoid not energised
Off
Solenoid button (10sec. On-10sec. Off)
On-Off
Linear power regulation (CCL option)
CR1
CR2
Variation of
capacity
NO2
NO3
NO8
NO9
Off
Load
Off
Stable function
Off
Drain to 50%
Off
Start/Stop
Solenoid energised by pulses
On
Solenoid not energised
Off
II.3
UNIT REMOTE CONTROL
II.3.1
Remote control with the control panel
installed on the unit or with a second
USM_CONTROL EQS_2335a21275_208549_210701_ES-EN-FR-DE-IT
Compressor valve
CR3
CR4
Circuit 1
NO4
NO5
Circuit 2
NO10
NO11
Off
On-Off
Off
On-Off
Off
On-Off
On-Off
On
Solenoid valve
CR3
CR4
compressor
NO4
NO5
NO10
NO11
Off
Off
On
Off
Off
Off
Off
Off
On
Off
Off
On
Note: for lengths exceeding 50 m and up to 200 m, the connection between KTR
and circuit board of the chiller/heat pump must be made using shielded cable AWG
20/22 (4 wires + shield) and two branching boards (use the KR200 E968573484
KIT) as in the layout shown below.
shielded cable AWG 20/22 (4 wires + shield) (not supplied)
C
Shield of the shielded cable
S
branching board (E968573484)
D
telephone cable (E968573484)
T
Circuit 1
II.3.2
Remote control by system automated and
Circuit 2
centralised control set-up
The connections between board and switch or remote light must be made with
shielded cable (make sure the shield is continuous throughout the length of the
cable) consisting of 2 twisted 0.5 mm² wires and the shield. The shield must be
connected to the earth screw on the panel (on one side only). The maximum
distance allowed is 30 m. Lay the cables far from the power cables or cables with
a different voltage and cables that emit electromagnetic disturbance. Do not lay
the cables close to equipment that could create electromagnetic interference.
Remote control selector switch
SCR
78
CONTROL EQS
(control with
potential free
contact)