5.2 Data table
Maximum operating pressure
Pump casing
Maximum suction pressure
Temperature range
Liquid temperatures
Ambient temperature
Electrical data
Motor efficiency
Motor Protection index
Insulation class
Frequency
Electrical voltage
Other data
Humidity
Altitude
Maximum suction head
Sound pressure level dB(A)
0/+3 dB(A)
5.3 Scope of deliveryt
• Multistage pump.
• Installation and operating instructions.
• Counterflange + screws and o'rings for PN16
configuration.
16
16, 25 ou 30 bars depend on the model
10 bars
Note : real inlet pressure (Pinlet)+ pressure at 0 flow delivered by the
pump must be below the maximum operating pressure of the pump. In
case of exceeding maximum operating pressure, the ball bearing and the
mechanical seal could be damaged or lifetime could decrease.
P Inlet + P at 0 flow ≤ Pmax pump
See pump nameplate to know the maximum operating pressure: Pmax
-30°C to +120°C
-15°C to +90°C (wiht FKM seal)
-20°C to + 120°C (with cast iron casing)
-15° to +40°C
Other temperature on request
Motor according to IEC 60034-30
IP55
155 (F)
See motor's rating plating
See motor's rating plating
< 90% sans condensation
< 1000 m
(> 1000m on request)
according to pump's NPSH
0.37 0.55 0.75 1.1 1.5 2.2
50Hz 56
57
58
62 64 68
60Hz 60
61
63
67 71 72
Power (kW)
3
4
5.5 7.5 11 15 18.5 22
69
71
74
74
78
81
WILO SE 01/2018
30 37 45
76
84