Operation on the supply system with grounded line conductor
Section 4.1.1, tables 4-1 and 4-2
The footnote 1) applies only to FSG converters, but not to FSH and FSJ converters.
Firmware version of the basic system
Section 7.1
[...]
• Firmware version of the basic system: [V04712708_1000102] V04712708_1010013
Operation under the conditions of environmental class 3C3
Section 11.3, footnote 3)
3)
Converters with installed [to be removed: BOP-2 or] IOP-2 are not designed for
operation under the conditions of environmental class 3C3. [...]
Automatic default settings of the load monitoring
Section 6.8.6.5: Blocking protection, leakage protection and dry-running protection
If you activate monitoring with p2193 the converter sets the following monitoring
parameters, depending on the application:
• p2193 = 4 or p2193 = 5:
o If p1080 < p0311 · 30%, then p2165 = p0311 · 30%
o If p1080 ≥ p0311 · 30%, then p2165 = p1080 + 5 rpm
o p2168 = r0333
o p2182 = p1080 - 0.01 rpm
o p2184 = p1082 + 0.01 rpm
o p2191 = r0333 · 20%
o p2181 = 7
• p2193 = 4:
o p2183 = (p1080 + p1082) / 2
o p2186 = r0333 · 30%
o p2188 = r0333 · 42.5%
o p2190 = r0333 · 80%
All default parameters can be changed at a later time.
If you deselect monitoring with p2193 < 4, the converter then resets the above-mentioned
parameters to factory settings.
Product information
Unrestricted
SINAMICS G120X, 12/2019
Page 2 of 3