3.5

GAS FEEDING LINE

Key to lay-out
1
– Gas supply pipe
2
– Manual cock (charged to the installer)
3
– Gas pressure gauge (charged to the installer)
4
– Filter
5
– Gas pressure switch
6
– Safety valve
7
– Pressure governor
8
– Adjusting valve
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
3.6
PROBE - ELECTRODE POSITIONING
Fig. 6
1
2
3.5 ±
0.3
D4020
20094559
1
2
3
M1
ATTENTION
Verify that the plate (1) is always inserted in the
flattening of the electrode (2).
ELECTRODE
PLATE
PROBE
7
GB
4
5
6
7
8
31 ±
0.3
Lean the probe insulator against the cup
M2
D5209
CUP