NOTE The redundant power source must be protected with Transient Voltage Surge
Suppression (TVSS).
2.
Plug the equipment to be protected into the appropriate UPS output
receptacles (see page 24 for more information on load segments).
Table 7. Plug Types Supported
IBM Plug Type
12
NOTE DO NOT protect laser printers with the UPS because of the exceptionally high
power requirements of the heating elements.
NOTE To prevent an overload alarm, verify that the total equipment ratings do not exceed
the UPS capacity.
3.
Verify that all load segment circuit breakers are in the ON position.
4.
Remove the breaker tie from all battery circuit breakers.
5.
Switch all battery circuit breakers to the ON position.
6.
Plug the UPS power cord into a power outlet.
μ
The
with the equipment offline.
7.
Press and hold the On button for approximately three seconds.
μ
The
display the percentage of load being applied to the UPS. The UPS is
now in Normal mode and supplying power to your equipment.
If the alarm beeps or a UPS alarm indicator stays on, refer to
"Troubleshooting" in the Powerware 5125 Rack-Mount UPS
(5000/6000 VA) User's Guide.
The UPS automatically sets the output voltage based on the input
voltage. To change the output voltage, see "Configuration Mode"
on page 28.
®
EATON Powerware
5125 (9910-P65) UPS Installation Guide for IBM
Description
NEMA L6-30P
IEC 320-C14
IEC 320-C20
indicator flashes, indicating the UPS is in Standby mode
indicator illuminates solid and the load level indicators
®
Applications
INSTALLATION
Quantity Supported
1
4
4
S
19
164201638 Rev A