OPERATION

Bypass Mode

In the event of a UPS overload or internal failure, the UPS transfers your
equipment to utility power. Battery mode is not available; however, the
utility power continues to be passively filtered by the UPS. The
S
S
S
S
S

Standby Mode

When the UPS is turned off and remains plugged into a power outlet,
the UPS is in Standby mode. The
indicators are off, indicating that power is not available to your
equipment. The battery recharges when necessary.
NOTE For 208–240V models, the output receptacles may remain electrically live (up to
110–120V). Unplug the UPS to ensure power is not available to the output receptacles.
40
EATON Powerware
indicator illuminates. The UPS transfers to Bypass mode when:
The UPS has an overtemperature condition.
The UPS has an overload condition of 103 to 112% for 2 minutes.
The UPS has an overload condition of 112 to 150% for up to
30 seconds.
The UPS detects a fault in the UPS electronics.
The UPS has been transferred to Bypass mode through the front
panel (see page 37).
®
9125 (9910-P64) UPS Installation Guide for IBM
μ
indicator flashes and the bar graph
®
S
Applications
164201637 Rev A