4.3.11.5 - DESCRIPTION OF DATE AND TIME CONFIGURATION SUB-MENU
DATE & TIME CONFIGURATION SUB-MENU
ITEM
FORMAT
COMMENTS
0
dAtE MEnu
When selected this item authorises return to the previous menu.
1
n
n n n
Current time setting.
1 2 3 4
00:00 to 23:59
n
n : hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours
1 2
can be adjusted.
n n
: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash and minutes can be adjusted.
3 4
2
Current day of week setting.
«Mon»
Monday
«tUe»
Tuesday
«uEd»
Wednesday
«tHu»
Thursday
«FrI»
Friday
«SAt»
Saturday
«Sun»
Sunday
3
n
n n n
Current day and month setting. The control mode is the same as for the time.
1 2 3 4
01:01 to 31:12
n
n :day (01 to 31).
1 2
n n
:month (01 to 12).
3 4
4
n
n n n
Current year setting.
1 2 3 4
5
YES/no
Summertime activation. One hour is added when summertime starts, and one hour is deducted when it ends. The time changes at 2.00 am.
6
nn
Summertime start month control.
7
Summertime start day of the week control.
«Mon»
Monday
«tUe»
Tuesday
«uEd»
Wednesday
«tHu»
Thursday
«FrI»
Friday
«SAt»
Saturday
«Sun»
Sunday
8
0 to 5
Summertime start week of the month control.
9
nn
Summertime end month control.
10
Summertime end day of the week control.
«Mon»
Monday
«tUe»
Tuesday
«uEd»
Wednesday
«tHu»
Thursday
«FrI»
Friday
«SAt»
Saturday
«Sun»
Sunday
11
nn
Summertime end week of the month control.
4.3.11.6 - DESCRIPTION OF THE TIME SCHEDULES
SUB-MENUS
The control provides two timer programs: schedule 1 and
schedule 2 that can be activated.
The fi rst timer program (schedule #1) provides a means
to automatically switch the unit from an occupied mode to
an unoccupied mode: the unit is started during occupied
periods.
The second timer program (schedule #2) provides a
means to automatically switch the active setpoint from
an occupied setpoint to an unoccupied setpoint: cooling
setpoint 1 is used during occupied periods, cooling or
heating setpoint 2 during unoccupied periods.
96
Program is in unoccupied mode unless a schedule time
period is in effect. If two periods overlap and are both active
on the same day, the occupied mode takes priority over
the unoccupied period.
Each of the eight periods can be displayed and changed
with the aid of a sub-sub-menu. The table below shows
how to access the period confi guration. Method is the
same for the time schedule #1 or the time schedule #2.

Hide quick links: