5.6 - CONTROL POINT

The control point represents the water temperature that the
unit must produce. The inlet water is controlled by default,
but the outlet water can also be controlled (requires a
Service confi guration modifi cation).
Control point = active setpoint + reset
5.6.1 - ACTIVE SETPOINT
Two setpoints can be selected as active in cooling mode
and two in heating mode. Usually, the second cooling
setpoint is used for unoccupied periods. The second
setpoint in heating mode is used for unoccupied periods.
LOCAL OPERATING MODE
PARAMETER STATUS
HEATING/COOLING
LOCAL SETPOINT
OPERATING MODE
SELECTION
Cooling
sp 1
Cooling
sp 2
Cooling [2]
Auto
Cooling [2]
Auto
Cooling
Auto
Cooling
Auto
Heating
sp 1
Heating
sp 2
Heating
Auto
Heating
Auto
REMOTE OPERATING MODE
PARAMETER STATUS
HEATING/COOLING
LOCAL SETPOINT
OPERATING MODE
SELECTION
Cooling [2]
sp control
Cooling
Cooling
Cooling [2]
Cooling [2]
Cooling [2]
Heating
Heating
REMOTE OPERATING MODE - DUAL-CIRCUIT UNITS
PARAMETER STATUS
HEATING/COOLING
ICE STORAGE
OPERATING MODE
CONFIGURATION [2]
Cooling
Cooling
Cooling [2]
activated
Cooling [2]
activated
Heating
Heating
2
Only with energy management option.
102
ICE STORAGE
CONFIGURATION [2]
activated
activated
deactivated
ICE STORAGE
CONFIGURATION [2]
activated
activated
activated
ICE STORAGE CONTACT
STATUS [2]
open
closed
Depending on the current operations, the active setpoint
can be selected by choosing the item in the Information
menu, with the user's volt-free contacts, with network
commands or with the setpoint timer program (schedule 2).
The following tables summarise the possible selections
depending on the control types (local, remote or CCN)
and the following parameters:
Setpoint select in local control: item #13 of the
Information menu permits selection of the active
setpoint, if the unit is in local operating type.
Heating/cooling operating mode.
Control contacts 2: status of control contact 2.
Schedule 2 status: schedule for setpoint selection.
ICE STORAGE CONTACT
SCHEDULE 2
STATUS [2]
STATUS
Unoccupied
open
Unoccupied
closed
Occupied
Unoccupied
Occupied
Unoccupied
ICE STORAGE CONTACT
STATUS [2]
open
closed
SCHEDULE 2 STATUS
Occupied
Unoccupied
Unoccupied
Unoccupied
Occupied
Unoccupied
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Ice storage setpoint
Cooling setpoint 2
Cooling setpoint 1
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2
Heating setpoint 1
Heating setpoint 2
ACTIVE SETPOINT
CONTROL
CONTACT 2
Control setpoint
sp 1 (open)
Cooling setpoint 1
sp 2 (closed)
Cooling setpoint 2
Open
Cooling setpoint 1
Closed
Ice storage setpoint
Closed
Cooling setpoint 2
sp 1 (open)
Heating setpoint 1
sp 2 (closed)
Heating setpoint 2
ACTIVE SETPOINT
Cooling setpoint 1
Cooling setpoint 2
Ice storage setpoint
Cooling setpoint 2
Heating setpoint 1
Heating setpoint 2