4.3.10.3 - MANUAL TESTS
This function allows the user to test the outputs individually,
if the machine is completely shut down (LOFF). To carry
out a manual test use the arrow keys to access the output
to be tested and press the Enter key (longer than 2
seconds) to activate the modifi cation mode. The password
is automatically requested, if it has not previously been
verifi ed. The Outputs/Test LED on the user interface begins
to fl ash. Enter the desired test value and again press Enter
to start the test. 'TESt' is displayed on the 4-digit display
alternately with the value tested. The Outputs/Test LED
stops fl ashing. Press the Enter key or an arrow key to
stop the test.
4.3.11- DESCRIPTION OF THE CONFIGURATION MENU
4.3.11.1- GENERAL
This menu can be used to display and modify all
confi gurations: Factory, Service and User. Only the User
Configuration can be modified by the end-user. The
Factory, Service and master/slave confi gurations are not
described in this document. A confi guration can only be
modifi ed if the unit is fully stopped (LOFF).
The menus User 1 [USEr 1] and User 2 [USEr 2] are
password-protected. The other menus are directly
accessible, except if item 11 of the User 2 menu (password
for all confi gurations) has been validated.
92
4.3.11.2 - PASSWORD
A password must be entered in order to access the test
function or to modify a confi guration. It is automatically
requested, if necessary: 'EntEr PASS' is displayed on the
4-digit display and the confi guration menu LED fl ashes,
indicating that the modifi cation mode is active. Press the
arrow keys until the value '11' is displayed on the 4-digit
display. Press Enter to validate this. The confi guration
menu LED stops fl ashing. If the password is correct, 'Good'
is displayed. If the password is incorrect, 'PASS incorrEct'
is displayed. The User password has a default value of 11.
This value can be modified through the Service
confi guration. The password can be entered if the unit
is fully stopped, otherwise 'ACCES dEniEd' (access
denied) will be displayed on the 4-digit display. The
controller automatically deactivates the password after
5 minutes without activity (i.e. no buttons pressed) or
after powering up.