4.3.11.4 - DESCRIPTION OF THE USER 2 CONFIGURATION SUB-MENU
USER 2 CONFIGURATION SUB-MENU
ITEM
FORMAT
0 [1]
USEr 2 Menu
1
«YES/no»
2
n
n n n
1 2 3
4
00:00 to 23:59
3
n
n n n
1 2 3
4
00:00 to 23:59
4
0 to 100
5
0 or 65 to 99
6
0 or 65 to 99
7
1 to 239
8
0 to 239
9
0/1/2/3/4
10
«YES/no»
11
«YES/no»
12
nnn
13 [1]
nnn
14 [1]
nnn
15
«YES/no»
*
n
n : hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.
1 2
n n
: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.
3 4
1
This item shall be masked when not used.
UNITS
COMMENTS
When selected this item authorises return to the previous menu.
-
Periodic pump quick-start of the water pump(s)
Yes = the pump is started periodically when the unit is manually stopped.
No = periodic pump start is disabled
When the unit is manually stopped (e.g. during the winter season) the pump is started each day at 14.00 hours
for 2 seconds. If two pumps are available, pump #1 is started on odd days and pump #2 on even days.
Night control mode - start time*
-
Authorises entering the time of day at which the night control mode starts. During this period the fan runs at
low speed (to reduce fan noise) and unit capacity is limited to the maximum night values.
Night control mode - end time*
-
Authorises entering the time of day at which the night control mode ends.
%
Minimum demand limit threshold in night mode. The unit capacity is never unloaded below this threshold,
when the night mode is active (low noise level).
-
Schedule 1 clock number (for unit on/off schedule, see section 4.3.11.6).
0 = schedule in local operating mode
65 to 99 = schedule in CCN operating mode
-
Schedule 2 clock number (schedule for setpoint selection, see section 4.3.11.6).
0 = schedule in local operating mode
65 to 99 = schedule in CCN operating mode
-
CCN element address.
No two network elements can have the same element number and bus number at the same time.
-
CCN bus number.
No two network elements can have the same element number and bus number at the same time.
-
User interface description text language
0 = English
1 = Spanish
2 = French
3 = Portuguese
4 = other (requires additional remote downloading)
-
Extended display selection.
YES = description of available menu
No = description of deactivated menu. This item permits activation or deactivation of the display showing the
menu items.
-
Activation of the user password for all user configurations: date, time schedules and broadcast.
-
Software version number.
This item shows the number of the software version used by this controller. Access is read only.
°C
Boiler activation temperature threshold. If the outside temperature is below this value, the boiler is started.
Free cooling outside temperature authorisation limit.
-
Ice storage authorisation mode.
YES : ice storage mode is authorised
No : ice storage mode is no authorised