Dräger Polytron 6100 EC WL Instrucciones De Uso página 47

Ocultar thumbs Ver también para Polytron 6100 EC WL:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 80
Bit
DIAG_STATUS
27
FAULTS_ELECTRONICS
26
FAULTS_SENSOR
25
INSTALLATION_CALIBRATION
24
OUT_OF_SERVICE
23
OUTSIDE_LIMITS
22
ENVIRONMENTAL
21
FAULT_PREDICTION
20
POWER_CRITICAL
19
POWER_LOW
18
SOFTWARE_UPDATE_INCOMPLETE
17
SIMULATION_ACTIVE
Instructions for use
|
Dräger Polytron
General status
Cause
F
Serious device fault, various causes.
F
Sensor not detected or defective.
C
Adjustment or bump test active.
C
Start sequence active.
Start sequence failed.
O
Transmitted gas reading below the mini-
mum range.
O
Gas detector is operated outside the
specified temperature range.
M
Device warning
F M
Battery charge critical.
M
Battery charge low.
C
Firmware update active
Firmware update failed.
C
Gas detector is in simulation mode.
®
6100 EC WL, Dräger Polytron
Remedy
A Restart the gas detector.
B Reset the gas detector to the factory
settings.
C Update firmware.
D Have the gas detector checked by
DrägerService.
A Check the sensor connection.
B Remove and reinstall the sensor.
C Change the sensor.
Finish calibration or bump test.
Wait for start sequence.
A Restart the gas detector.
B Have the gas detector checked by
DrägerService.
A Calibrate the gas detector.
B Change the sensor.
Use weather protection kit (accessory)
when exposed to sunlight.
A Check ISA100 Wireless
B Check detail status with PolySoft.
Change battery pack immediately.
Change battery pack soon.
Wait for firmware update (maximum 15 min-
utes).
A Restart the gas detector.
B Have the gas detector checked by
DrägerService.
Exit simulation mode via PolySoft.
®
Repeater ISA
|
en
Troubleshooting
connection.
47

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Polytron repeater isa

Tabla de contenido