Operation Instructions
will be the default value (18 ).
③ At the "WEEKLY TIMER" setting page there are totally three setting types for each day
"√": it indicates once the Week Timer is activated, the timer on this day is effective and will not be
affected by the "Holiday" mode.
"×": it indicates even if the Week Timer is activated, the timer on this day is ineffective.
"Holiday": it indicates when the Week Timer is activated but "Holiday" is not activated, then the
timer on this day is effective; when "Holiday" is also activated, the timer on this day is ineffective.
④ When "Weekly timer" has already been set and the concerned modes include "Hot water",
if resetting "Water tank" from "With" to "Without", then "Hot water" mode will be automatically
changed to "Heat", "Cool+hot water"/ "Heat+hot water" changed to "Cool"/ "Heat".
⑤ Temperature Setpoint
The control is able to decide the temperature type and temperature range based on the current
"Clock Timer", "FCU", "T-water Ctrl.", and "Ctrl. state" settings. See the followings for more details.
If the set mode is "Hot water", the temperature set point shows nothing, indicating there is no
need to set "T-water out" and "T-room" but only "T- tank". If the set mode "Cool" or "Heat", then
water tank temperature box will show nothing, indicating there is no need to set "T-tank".
Ctrl.
Set
state
Mode
Cool
T-water
out
Heat
Cool
T-room
Heat
2.2.13 Clock Timer
This function will make the unit run with certain modes in certain periods within a day based on
the user's actual demand.
[Operation Instructions]
1. At the homepage, by pressing the Function key
then locate where "Clock timer" is, after that, press OK key
page.
Object
Water out
7-25°C
temperature for
(With FCU)
cooling(WT-cool)
Water out
High temp.
temperature for
Low temp.
heating(WT-heat)
Room
temperature for
cooling(RT-cool)
Room
temperature for
heating(RT-heat)
Range
18-25°C
(Without
18°C(Without FCU)
FCU)
25-61°C
25-55°C
18-30°C
18-30°C
access to the FUNCTION page, and
to go to the COLCK TIMER setting
13
Default
Accuracy
7°C(With FCU)
45°C
35°C
24°C
20°C
1°C
1°C
1°C
1°C
1°C