Adjusting Window Treatment Settings
Setting Limits
Note: Entering Limit Setup mode
may cause window treatments to
move approximately 8 inches up
or down. Be sure that each
window treatment is positioned
so that the fabric can safely
move 8 inches up or down
before entering Limit Setup
mode.
1.On any shade column,
press and hold
simultaneously the top
and raise buttons. The
LEDs next to the top
and bottom buttons will
cycle.
Note: At any time while
in Limit Setup mode,
you can move all
window treatments
together to their current
open limit by double-
tapping the top button,
or to their current close
limit by double-tapping
the bottom button.
Note: Once EDUs (electronic drive units
of the window treatment) have been
assigned to shade columns, limits can be
set for an EDU only using the shade
column it is assigned to, and a shade
column can set limits only for those EDUs
assigned to it.
R
2.Select the EDU you want to to adjust
using the top button on the shade
column. Each time you press and release
the top button, a different EDU that is
assigned to that shade column will open
and close in an 8-inch range to indicate it
is selected. Press the top button until the
EDU for the window treatment you wish
to adjust moves. (You can also use the
bottom button, which moves through the
assigned EDUs in the opposite order.)
3. Adjust the currently selected
EDU to the desired level for
the open limit (the maximum
the window treatment is
allowed to open) using the
raise and lower buttons.
4.Press and hold the top button on the
shade column for 5 seconds to store the
current position as the open limit. The
LED next to the top button will flash
quickly for 2 seconds.
5.Adjust the currently selected EDU to the
desired level for the close limit (the
maximum the window treatment is
allowed to close) using the raise and
lower buttons.
6.Press and hold the bottom button on the
shade column for 5 seconds to store the
current position as the close limit.The
LED next to the bottom button will flash
quickly for 2 seconds.
7.Repeat steps 2 through 6 to set the open
and close limits for each window
treatment assigned to the shade column.
8.Press and hold simultaneously the top
and raise buttons on the shade column to
exit Limit Setup mode.
GRAFIK Eye