Qs System Low-Voltage Control Wiring - Lutron GRAFIK Eye QS Serie Manual De Montaje Y Utilización

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

QS System Low-Voltage Control Wiring

• System communication uses PELV (Class
2: USA) low-voltage wiring.
• Follow all local and national electrical
codes when installing PELV (Class 2:
USA) wiring with line voltage/mains
wiring.
• Each terminal accepts up to two #18
AWG (1.0 mm
2
) wires.
• Total length of control link must not
exceed 2000 ft. (610 m).
• Make all connections in the control unit's
wallbox.
• A QS system can have up to 100 zones
and 100 devices (see table below).
• Wiring can be T-tapped or daisy-chained.
• Wire sizes:
- Two #18 AWG (1.0 mm
2
) conductors for
control power.
- One twisted, shielded pair of #22 AWG
(1.0 mm
2
) for data link.
- Cable is available from Lutron:
GRX-CBL-S-500 (non-plenum)
GRX-CBLP-S-500 (plenum rated).
Check compatibility in your area.
System Limits
QS Device
3-zone QS
LUTRON
4-zone QS
LUTRON
6-zone QS
LUTRON
seeTouch QS
LUTRON
Sivoia QS
QS smart power supply panel
R
T-Tap Wiring Example
GRAFIK Eye QS
QS smart
power
supply panel
Sivoia QS
Daisy-Chain Wiring Example
GRAFIK Eye QS
LUTRON
Zone Count
Device Count
3
1
4
1
6
1
0
1
1
1
0
1
seeTouch QS
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
Sivoia QS
LUTRON
LUTRON
QS smart power
supply panel
GRAFIK Eye
QS System Installation and Operation Guide 5
®
seeTouch QS
LUTRON
LUTRON
LUTRON
LUTRON