Fan; Arc Detection - Fronius Symo Advanced 10.0-3 208-240 Manual De Instrucciones

Ocultar thumbs Ver también para Symo Advanced 10.0-3 208-240:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Factory setting
CO2 factor
Set the CO2 factor for the energy fed into the grid

Fan

For testing the fan functionality
Setting range
-
-
-
IMPORTANT! The inverter display does not indicate whether the fan is OK. The
fan function can only be checked by listening and feeling.

Arc Detection

for checking arc detection/interruption
Setting range
Arc.det. Status
displays the current status of arc detection/interruption
Start Self-test
self-test to check whether the inverter interrupts grid power feed operation
when an arc is detected.
Test procedure:
1
2
3
4
The self-test starts. The arc detection/interruption function simulates an arc
and sends the corresponding signal to the inverter.
If the test is successful, the inverter disconnects from the grid and stops grid
power feed operation.
The message "Self-test completed and Start AFCI" is shown on the display.
5
(depends on the country setup)
Test fan #1/test fan #2 (depending on the device)
Select the desired fan using the "Up" and "Down" keys
Pressing the "Enter" key starts the test for the selected fan.
The fan runs until the menu is exited by pressing the "Esc" key.
ArcDetector Status/Start Self-test
Select "Arc Detection" in the Setup menu
Press the "Enter" key
Use the up and down keys to select "Start Self-test"
Press the "Enter" key
Confirm the indication by pressing the "Enter" key