ERROR
MALFUNCTION OR
CODE
PROTECTION
High pressure protection
Compressor overcurrent
protection.
Compressor discharge temp,
too high protection
High Temperature difference
protection between water inlet
and water outlet of the plate
heat exchanger.
22T÷30T
Heating mode, DHW mode:
1. The water flow is low; water temp is high, whether there is air in the water
system. Release the air.
2. Water pressure is lower than 0.1 Mpa, charge the water to let the pressure
in the range of 0.15~0.2Mpa.
3. Over charge the refrigerant volume. Recharge the refrigerant in right
volume.
4. Electrical expansion valve locked or winding connector is loosen. Tap-tap
the valve body and plug in/ plug off the connector for several times to make
sure the valve is working correctly. And install the winding in the right location
DHW mode: Water tank heat exchanger is smaller than the required 1.7m2.
(10-16kW unit)or 1.4m2 (5-9kW unit) Cooling mode:
1. Heat exchanger cover is not removed. Remove it.
2. Heat exchanger is dirty or something is block on the surface. Clean the
heat exchanger or remove the obstruction.
1. The same reason to P1.
2. Power supply voltage of the unit is low, increase the power voltage to the
required range.
1. The same reason to P1.
2. System is lack of refrigerant volume. Charge the refrigerant in right
volume.
3. TW_out temp sensor is loosen Reconnect it..
4. T1 temp sensor is loosen. Reconnect it.
5. T5 temp sensor is loosen. Reconnect it.
1. Check that all shut off valves of the water circuit are completely open.
2. Check if the water filter needs cleaning.
3. Refer to "9.4 Charging water"
4. Make sure there is no air in the system (purge air).
5. Check on the manometer that there is sufficient water pressure. The water
pressure must be >1 bar (water is cold).
6. Check that the pump speed setting is on the highest speed.
7. Make sure that the expansion vessel is not broken.
8. Check that the resistance in the water circuit is not too high for the pump,
(refer to "10.6 Setting the pump speed").