6.2 Selecting a location in hot climates
As the outdoor temperature is measured via the outdoor unit air thermistor, make sure to install the outdoor unit in the shade
or a canopy should be constructed to avoild direct sunlight, so that it is not influenced by the sun's heat, otherwise protection
may be possible to the unit.
7 INSTALLATION PRECAUTIONS
7.1 Dimensions
Model
A
22T/26T/30T
1129
7.2 Installation requirements
•
Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during its
operation.
•
In accordance with the foundation drawing in the figure, fix the unit securely by means of foundation bolts. (Prepare six
sets each of Փ10 Expansion bolts, nuts and washers which are readily available in the market.)
•
Screw in the foundation bolts until their length is 20 mm from the foundation surface. (unit: mm)
(unit: mm)
Փ10 Expansion
bolt
Rubber
shocking
proof mat
Solid
ground or
roofing
90
EN
B
C
D
E
494
528
668
192
Concrete basement
h≥100mm
Cod. 3QE47660 - Rev. 00 - 02/2022
OMNIA M 3.2
F
G
H
I
98
206
1558
558
22T÷30T
J
K
L
143
400
440