Descargar Imprimir esta página

Acuity Brands Lithonia Lighting TCC Manual De Instrucciones página 3

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTRUCTIONS FOR Lithonia Lighting TCC
IMPORTANT: Provide each unit with a single-phase AC un-switched power supply from a circuit used for normal lighting.
"UVOLT" product versions operate from 120 volts through 347 volts. PRODUCT DAMAGE WILL OCCUR IF THE RATED INPUT VOLTAGE IS EXCEEDED.
NOTE: The battery must be connected to the charger board prior to applying AC power to the unit. Battery damage may occur if the battery is connected longer than 24
hours without continuous AC power provided. See also "Important Battery Information".
NOTE: The maximum mounting height of TCC 350L from ground is 17.1 feet, TCC 750L and TCC 750L HO from ground is 25.4 feet to meet the minimum illumination
requirements of NFPA 101 (current Life Safety Code).
NOTE: Do not connect battery or power unit until remote units (if applicable) are fully connected and wires are isolated from other potentials (i.e. remote wires shall be
isolated from earth ground).
NOTE: Supports 4" Square, 4" Octagon or a single rectangular (4"x 2.125") J-Box.
1. Remove the side cover by unscrewing two side screws and remove side cover. (See Fig A)
2. Slide out front panel, if applicable, to permit installation process. Installer will need to remove bonding screw on Standard
Exit Signs.
SIDE SCREWS
J-BOX HOLES
NOTE: for side mounting of lampheads see section Side Mounting Lampheads.
3. Mounting options:
J-Box Mounting: knock out the appropriate mounting pattern and the wire pass hole in the backplate to fit the J-box
being used. Approved J-Box sizes are 4" Square (With or without plaster ring), 4" Octagon, or a single rectangular J-
Box.
Conduit Mounting: knock out the appropriate conduit and mount the backplate to the wall in the desired location
using the keyhole knockouts (See Fig. A). Attach a conduit hub to desired conduit mount hole on the frame. An
additional screw may be required at the j-box center bottom hole to pull the unit back into the wall as visible from
the bottom of the unit. Do not use center knockout if the HO option is used to prevent interference of the conduit
with the battery.
PAGE: 2 of 19
LED Steel Combo Emergency Unit
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
BACK MOUNT INSTALLATION
SAVE THESE INSTRUCTIONS
and deliver to owner after installation
KEY HOLES
BONDING SCREW
Fig. A
CONDUIT MOUNT
KNOCKOUTS
Standard Exit Sign

Publicidad

loading