INSTALLATION
Installation. is. permanent. and. must.
exclusively.be.performed.by.specialised.
and. qualified. personnel,. following. all.
the. instructions. and. provisions. inclu-
ded.in.this.manual..Current.regulations.
must.also.be.met.
2.1
SUPPLY
"DEWY EQUIPE P100 and P200 BOX"
heat.modules,.inter-connectible.by.flan-
ge,. are. supplied. with. an. external. pre-
painted.zinc-coated.laminate.case..
They. are. complete. with. supply/return.
water. manifold. fastening. screws. and.
gaskets.and.sequence/cascade.digestion.
unit. code. 8096301. supplied. with. "P100-
P200-P300-P400 BOX". modules. and.
code.8096308.supplied.with."P500-P600
BOX".modules.
Available.separately:
–. Safety. kit. code. 8101524. for. modu-
les.
"P100-P200-P300-P400
BOX". and.code.8101525.for.modules.
"P500-P600 BOX"
–. Double. box. (size:. 1100. x. 790. x. 1600).
for. hydraulic. separator/safety. kit. and.
distributors,.code.8101527.(figure.4).
–. Hydraulic. separator. kit. code. 8101552.
for. modules. "P100-P200-P300-P400
BOX".
and. code. 8101553. for. modules.
"P500-P600 BOX"
FOR MODULES "P100-P200-P300-P400 BOX"
BOX CONTENITORE DOPPIO PER COMPENSATORE
IDRAULICO E KIT SICUREZZE INAIL cod. 8101527
PER "MURELLE EQUIPE 220 - 330 BOX ErP"
FOR MóDULES "P500-P600 BOX"
BOX CONTENITORE DOPPIO PER COMPENSATORE
IDRAULICO E KIT SICUREZZE INAIL cod. 8101527
PER "MURELLE EQUIPE 440 - 550 - 660 BOX ErP"
62
–. Polypropylene.exhaust.manifold.kit.for.
indoor. installation. (purposely. treated.
to. resist. weathering. when. installed.
outdoors):
. code.8102510.for."P100 BOX" module
. code.8102530.for."P200 BOX" module
. code.8102531.for."P300 BOX" module
. code.8102532.for."P400 BOX" module
. code.8102533.for."P500 BOX" module
. code.8102534.for."P600 BOX" module
–. Exhaust. terminal. code. 8089530. for.
outdoor.installations.
To.electrically.connect.the.modules.and.
to.assemble.the.exhaust.for.indoor.or.ou-
tdoor.installations,.see.points.2.6,.2.7.and.
2.10.in.this.manual.
2.2
INSTALLATION
2.2.1
Indoors
"DEWY EQUIPE P100-P200-P300-P400-
P500-P600 BOX". heat. modules. can. be.
installed.in.boiler.rooms.whose.size.and.
requirements.meet.current.regulations.
Furthermore,. vents,. with. surface. areas.
at. least. . 3.000. sq.. cm. . or. . 5.000. sq.. cm.
for. gas. with. density. over. 0.8,. must. be.
installed. in. the. outer. walls. for. room.
ventilation..
396
1100
790
396
1100
790
2.2.2
Outdoors
"DEWY EQUIPE P100-P200-P300-P400-
P500-P600 BOX". heat. modules. can.
also. be. installed. outdoors. with. the. spe-
cific. exhaust. for. single. module. code.
8089530.
2.3
SYSTEM CONNECTIONS
To.protect.the.heat.system.from.damaging.
corrosion,. incrustation. or. deposits,. after.
installation. it. is. extremely. important. to.
clean.the.system.using.suitable.products.
such.as,.for.example,.Sentinel X300 (new
systems), X400 and X800 (old systems)
or Fernox Cleaner F3..Complete.instruc-
tions.are.provided.with.the.products.but,.
for. further. information,. you. may. direct-
ly. contact. SENTINEL. PERFORMANCE.
SOLUTIONS. LTD. or. FERNOX. COOKSON.
ELECTRONICS.. For. long-term. protection.
agains. corrosion. and. deposits,. the. use.
of. inhibitors. such. as. Sentinel X100 or
Fernox Protector F1. is. recommended.
after.cleaning.the.system..It.is.important.
to. check. the. concentration. of. the. inhibi-
tor. after. each. system. modification. and.
during. maintenance. following. the. manu-
facturer's. instructions. (specific. tests. are.
available.at.your.dealer)..The.safety.valve.
drain. must. be. connected. to. a. collection.
NOTE:
move the flanges fixed to the box wall with
screws and place them in the location shown
in the figure, depending on the type of hydrau-
lic separator used.
Fig..4