6. PRACTICAL EXAMPLES OF ELECTRICAL TESTS
6.1
LOW CONTINUITY MEASUREMENT
CONTINUITY MEASUREMENT ON PROTECTIVE CONDUCTORS
PURPOSE OF THE TEST
Check the continuity of:
NOTE: This test is to be preceded by a visual check verifying the existence of yellow-
green protective and equalising potential conductors as well as compliance of
the sections used with the standards' requirements.
INSTALLATION PARTS TO BE CHECKED.
Equalising
potential node
Examples for continuity measurement on conductors
protective conductors (PE), main equalising potential
conductors
(EQP),
conductors (EQS) in TT and TN-S systems.
neutral conductors having functions of protective
conductors (PEN) in TN-C system.
25
secondary
equalising
Connect one of the
test leads to the
protective conductor
of the FM
and the other to the
equalising potential
node of the earth
installation.
Connect one of the
test
external
this case the water
pipe) and the other
to
installation using for
example
protective conductor
of the closest FM
socket.
potential
socket
lead
to
the
mass
(in
the
earth