salmson SIE BV Serie Instalacion Y Puesta En Servicio página 50

Ocultar thumbs Ver también para SIE BV Serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

English
Connections of the signal inputs
and outputs
42
DANGER! Risk of fatal injury!
Contact voltage dangerous to human life
Work on the module may only be started once 5 minutes have
passed, due to the dangerous residual contact voltage (capacitors).
• Before working on the pump, disconnect the supply voltage and
wait for 5 minutes.
• Check whether all connections (including potential-free contacts)
are voltage-free.
CAUTION! Risk of damage!
Risk of damage due to inappropriate handling.
• Do not connect any external voltage. That could destroy the
module.
(Terminal 1, output): +10 V DC
Power supply for signal connection terminals
(Terminal 2, analogue input): 0...10 V/0...20 mA
As external setpoint signal
Conversion between voltage and current signals:
• 0...10 V
via switch position S3
• 0...20 mA
via switch position S3
The frequency and thus the speed or the set pressure follow the volt-
age or, if a current signal is chosen, the current (Fig. 10 + 11).
(Terminal 3, analogue input): 0...10 V/0...20 mA (1)
As external actual value signal (setting for differential pressure
sensor)
Conversion between voltage and current signals:
• 0...10 V
via switch position S4
• 0...20 mA
via switch position S4
(Terminal 4, output): +24 V (3)
DC voltage for an ext. consumer/sensor. The voltage is short-circuit
proof.
(Terminal 7/15, output): GND (2)
Earth connections for signal inputs (0...10 V/0...20 mA).
(Terminal 10, digital input): operating mode
Switching between pressure controlled operation (Δp-c) or manual
control mode (n-const):
• Δp-c
Bridge to terminal 5
• n-const
Bridge to terminal 5
(Terminal 18, digital input): Ext. off
Setting of the Ext. off function:
• Release
Bridge to terminal 11 closed (factory setting)
• Block
Bridge to terminal 11 open
If the contact is closed, the module is ready for operation.
If the contact is open, the pump is switched off.
NOTE
With a DIE...BV, the changes to terminals 10 and 18 are to be made on
the master only.
(Terminals 31-32-33, output): SBM (collective run signal);
potential-free changeover contact
During operation of the pump, the corresponding contacts as
• NC contact
between terminals 31 + 32 are
• NO contact
between terminals 31 + 33 are
(factory setting)
(factory setting)
closed
open
open
closed
Pompes Salmson 03/2011

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Die bv serie

Tabla de contenido